Faults - Possible Causes - Solutions - Riello DB 9 LSE FGR Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burner, two stage progressive or modulating operation
Table of Contents

Advertisement

7

Faults - Possible causes - Solutions

If faults arise in ignition or operations, the burner performs a
"safety stop", which is signalled by the red burner lockout LED.
The display visualises alternately the lockout code and the
relative diagnostic. To reset the start-up conditions, refer to the
"Reset procedure" indicated in the control box manual supplied.
When the burner starts again, the red LED goes out and the
control box is reset.
OIL OPERATION
Problem
The burner does not start
The burner does not come on and
the lockout appears
The burner starts and then goes
into lockout
The burner turns on and then
remains in lockout mode
Once the pre-purging and the
safety time has elapsed the
burner goes into lockout without
the flame appearing
Locks out with
flame
Burner goes into lockout during
operation
Lockout when the burner stops
Ignition with pulsations
Faults - Possible causes - Solutions
Probable cause
• No power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . Turn off switches - Check wiring
• A limit or safety control device is open . . . . . . . . . . Adjust or replace it
• Flame control lockout . . . . . . . . . . . . . . . . . . . . . . . Release
• Control box fuse broken . . . . . . . . . . . . . . . . . . . . . Replace it
• Incorrect electrical wiring. . . . . . . . . . . . . . . . . . . . . Check connections
• Defective flame control . . . . . . . . . . . . . . . . . . . . . . Replace it
• Air pressure switch in operating position. . . . . . . . . Adjust it or replace it
• Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace control box
Air pressure switch does not switch owing to lack of air pressure:
• Air pressure switch is badly adjusted . . . . . . . . . . . Adjust it or replace it
• Pressure switch pressure test point pipe blocked . . Clean
• Head incorrectly adjusted . . . . . . . . . . . . . . . . . . . . Adjust
• Defective flame detection circuit . . . . . . . . . . . . . . . Replace control box
• The VR solenoid valve lets too little gas through . . Increase it
• The VS solenoid valve does not open. . . . . . . . . . . Replace the coil or the panel
• Firing transformer defective. . . . . . . . . . . . . . . . . . . Replace it
• Incorrect valve or firing transformer connections . . Redo
them
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . . Replace
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . . Replace
• Fault on air pressure switch . . . . . . . . . . . . . . . . . . Replace
• Permanent flame in the head or flame simulation . . Eliminate permanency of flame or
combustion or flame simulation
• Head incorrectly adjusted . . . . . . . . . . . . . . . . . . . . Adjust
• Incorrectly adjusted fan air damper: too much air . . Adjust
• Firing output too high. . . . . . . . . . . . . . . . . . . . . . . . Reduce it
35
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row. If the burner
locks out for a third time, contact the customer
ATTENTION
service.
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
DANGER
manual and in compliance with the standards and
regulations of current laws.
rectifier
or replace control box
GB
Suggested remedy