Faults - Possible causes - Solutions

If faults arise in ignition or operations, the burner performs a
"safety stop", which is signalled by the red burner lockout LED.
The display visualises alternately the lockout code and the rela-
tive diagnostic. To reset the start-up conditions, refer to the "Re-
set procedure" indicated in the control box manual supplied.
When the burner starts again, the red LED goes out and the con-
trol box is reset.
GAS OPERATION
Problem
The burner does not start
The burner does not come
on and the lockout appears
The burner turns on and
then stops in lockout mode
The burner turns on and
then remains in lockout
mode
Once the pre-purging and
the safety time has elapsed
the burner goes into lockout
without the flame appearing
Locks out with
flame
The burner continues to
repeat the start-up cycle,
without lockout
Faults - Possible causes - Solutions
Possible cause
• No electrical power supply . . . . . . . . . . . . . . . . . . . . Close all switches - Check connections
• A limiter or safety control device is open . . . . . . . . . Adjust or replace
• Control box lockout . . . . . . . . . . . . . . . . . . . . . . . . . Unlock control box
• Control box fuse broken. . . . . . . . . . . . . . . . . . . . . . Replace it
• Incorrect electrical wiring . . . . . . . . . . . . . . . . . . . . . Check connections
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . . Replace
• No gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Open the manual valves between meter and
• Mains gas pressure insufficient . . . . . . . . . . . . . . . . Contact your GAS COMPANY
• Minimum gas pressure switch fails to close . . . . . . . Adjust or replace
• Air pressure switch in operating position . . . . . . . . . Adjust or replace
• Flame simulation. Replace the control box
Air pressure switch does not switch owing to lack of air pressure:
• Air pressure switch is badly adjusted. . . . . . . . . . . . Adjust it or replace it
• Pressure socket tube of the pressure switch clogged. Clean it
• Head badly adjusted. . . . . . . . . . . . . . . . . . . . . . . . Adjust it properly
• Defective flame detection circuit . . . . . . . . . . . . . . . Replace control box
• The VR solenoid lets too little gas through. Increase it
• The VR or VS solenoid valve does not open. Replace the coil or the rectifier panel
• Gas pressure too low . . . . . . . . . . . . . . . . . . . . . . . . Increase pressure at regulator
• The burner's pilot is not functioning. . . . . . . . . . . . . Check
• Firing transformer defective. . . . . . . . . . . . . . . . . . . Replace it
• Incorrect valve or firing transformer connections. . . Redo them
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . . Replace
• A closed valve up-line from the gas train . . . . . . . . . Open it
• Air in pipework . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bleed air
• The VR solenoid lets too little gas through. . . . . . . . Increase it
• Maximum gas pressure switch intervention . . . . . . . Adjust or replace
• Defective control box . . . . . . . . . . . . . . . . . . . . . . . . Replace
• The gas pressure in the network is near the value. . Reduce the cut in pressure of the min. gas
pressure switch on which the min. . . . . . . . . . . . . . . gas pressure switch is adjusted.
The sudden fall in pressure that follows. . . . . . . . . . Replace the gas filter cartridge
the opening of the valve causes the temporary opening
of the pressure switch itself immediately
the valve closes and the burner stops. The
pressure starts to increase again. The pressure switch
closes and repeats the start up cycle.
The sequence repeats endlessly.
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row. If the burner
locks out for a third time, contact the customer
WARNING
service.
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
DANGER
manual and in compliance with the standards and
regulations of current laws.