9-3. INSTRUCTION OF TROUBLESHOOTING
Start
Indoor unit
operates.
Outdoor unit
does not
operate.
Outdoor unit
Outdoor unit
operates only
does not
in Test Run
operate
operation.
even in
Test Run
operation.
Refer to
Check room
"How to check
temperature
inverter/
thermistor.
compressor".
Refer to 9-7.
"Test point
diagram and
voltage".
Left lamp
Left lamp
Blink ON and
2-time blink
OFF at
Cause:
0.5-second
Indoor unit
intervals
• Trouble of
Cause:
room temp-
Indoor/
erature/
Outdoor unit
indoor coil
• Miswiring
thermistor
or trouble
of serial signal
Check room
Refer to 9-6.
temperature
"How to
thermistor
check
and indoor
miswiring
coil thermis-
and serial
tor.
signal error
Refer to 9-7.
(when
"Test point
outdoor unit
diagram and
does not
voltage".
work)".
OBHT752
Indoor unit operates.
Outdoor unit does
not operate normally.
Indoor unit
Unit does
operates, when
not operate
EMERGENCY
normal
OPERATION
operation in
switch is pressed.
COOL or
HEAT mode.
Refer to
Refer to 9-6.
"Check of
"Check of
R.V. coil".
remote controller,
display receiver
P.C. board and
indoor control
P.C. board".
Left lamp
Left lamp
3-time blink
4-time blink
Cause:
Cause:
Indoor unit
Indoor unit
• Trouble of
• Trouble of
indoor fan
indoor unit
motor
control
system
Refer to 9-6.
Replace the
"Check of
indoor
indoor fan
electronic
motor".
control
P.C. board.
Indoor unit does
OPERATION INDICATOR
not receive
lamp on the indoor unit is
the signal from
flashing ON and OFF.
remote controller.
Indoor unit
does not operate,
when
EMERGENCY
OPERATION
switch is pressed.
1. Check indoor / outdoor
connecting wire.
(Check if the power
is supplied to the
indoor unit.)
2. Refer to 9-6.
"Check of indoor
electronic control
P.C. board and indoor
fan motor".
Left lamp
Left lamp
5-time blink
6-time blink
Cause:
Cause:
Outdoor unit
Outdoor unit
• Outdoor
• Trouble of
power
thermistor
system
in outdoor
abnormality
unit
Refer to
Refer to
"How to check
"Check of
the inverter/
outdoor
compressor".
thermistors".
25
If blinking of OPERATION
INDICATOR lamp cannot be
checked, it can be checked with
failure mode recall function.
"Test Run operation" means the
operation within 30 minutes after
EMERGENCY OPERATION switch
is pressed.
Refer to outdoor unit service manual.
Left lamp
Left lamp
7-time blink
14-time blink
Cause:
or more
Outdoor unit
Cause:
• Trouble of
Outdoor unit
outdoor
• Other
control
abnormality
system
Check
Replace the
"Flow chart of
inverter P.C.
the detailed
board or
outdoor unit
the outdoor
failure mode
electronic
recall function."
control P.C.
board.