13-6. ROTATION SETTING
Setting method of each function by wired remote controller
■ PAR-41MAA
1. Stop operation
Select "Service" from the Main menu, and press the [
Select "Settings" with the F1 or F2 button, and press the [
Select "Rotation setting" with the F1 or F2 button, and press the [
2. Set the rotation function.
Select "Rotation" with the F1 button.
Select the rotation period or "Backup only" with the F2 or F3 button.
■ "Rotation" setup
None, 1 day, 3 days, 5 days, 7 days, 14 days, 28days, Backup only
Notes:
When 1 to 28 days are selected, the backup function is also enabled.
When "Backup only" is selected, the rotation function will be disabled. The sys-
tems with refrigerant addresses of 00 or 01 (00 system/ 01 system) will be oper-
ated as a main system while the 02 system is the standby mode as backup.
3. Set the support function.
Select "TempDifTrigger" with the F1 button.
Select "the difference between the suction temperature and the set tempera-
ture" with the F2 or F3 button.
■ "TempDifTrigger" setup
None, +4ºC, +6ºC, +8ºC
Notes:
The support function is available only in the COOL mode. (Not available in the
HEAT, DRY and AUTO mode.)
The support function is enabled when any option other than "None" is selected
from the "Rotation" setup.
4. Update the setting.
Press the [
] button to update the setting.
Reset method
Press the F4 button in step
will start from the 00 or 01 systems.
Note: When the 01 system is in the backup operation, the 00 systems will be operated again.
OCH784
] button.
to reset the operation time of the rotation function . Once it is reset, operation
or
59
Function setting
Rotation setting
Service menu:
F1
] button.
] button.
Rotation
TempDifTrigger
Select :
Cur.
F1
Rotation
TempDifTrigger
Select :
Cur.
F1
Settings menu
Cursor
F2
F3
F4
Rotation setting
Backup only
+4°C
− Content +
R
e
s
t e
F2
F3
F4
Rotation setting
Backup only
+4°C
− Content +
R
e
s
t e
F2
F3
F4