Mitsubishi Electric PLA-SM71EA2 Service Manual page 40

Split-type, heat pump air conditioners, ceiling cassettes r32/r410a, indoor unit, grille
Table of Contents

Advertisement

OPERATING PROCEDURE
12. Removing the drain pump (DP)
(1) Remove the drain pan. (Refer to procedure 10)
(2) Cut the hose band and remove the hose.
(3) Loosen the clamp of the drain pump.
(4) Remove the drain pump (tapping screw 4×10: 2 screws/2
hooks).
(5) Cut the drain pump base and lead wire fixing band.
(See Figure 5)
(6) Remove the lead wire of the drain pump from the clamp
of the drain pump base. (See Figure 5)
(7) Remove the drain pump (tapping screw: 3 screws).
(See Figure 6)
Figure 6
OCH784
Tapping screws
PHOTOS/FIGURES
Photo 15
Drain pump
Clamp
Drain pump base
fixing screws
Figure 5
Drain pump base and lead wire fixing band
40
Float switch
Hose band
Float switch fixing screw
Clamp of the
drain pump base