Fujitsu AG G12LVCA Series Service Instruction page 60

Hide thumbs Also See for AG G12LVCA Series:
Table of Contents

Advertisement

For AO*G14LVLA
SERVICE PARTS INFORMATION 6
Active filter module
Check Point 1 : Check Open or Short-circuit and Diode (D1)
Remove connector, check the open or short-circuit and the diode in the module
L1
+IN
-IN
If it is abnormal,replace ACTIVE FILTER MODULE
Check Point 2 : Check the Output DC voltage (between P and N)
Check the Output DC voltage (between P and N) of compressor stopping and operating.
>> If the output voltage of compressor operating is less than the output voltage of compressor stopping,
Active Filter Module is detective. >> Replace Active Filter Module
L2
P
N
Check the open or short-circuit
Terminal
Tester(+)
Tester(-)
(+IN)
( IN)
( IN)
N
(+IN)
P
L2
L1
N
P
Control Box
L1,L2
L2
N
Check the diode
Terminal
Tester(+)
Tester(-)
L2
P
P
L2
Ref. value 1
Specifications for Multimeter
Manufacturer : HIOKI
Model name
: 3804
Power source : DC9V.
02-35
Resistance value
+ -
360k
20%
0
+ -
720k
20%
1.40M
/
2.28M
(Ref. value 1)
(Ref. value 2)
+ -
360k
20%
1.69M
/
1.88M
(Ref. value 1)
(Ref. value 2)
Resistance value
1.32M
/
1.50M
(Ref. value 1)
(Ref. value 2)
1.40M
/
1.51M
(Ref. value 1)
(Ref. value 2)
Ref. value 2
Specifications for Multimeter
Manufacturer : YOKOGAWA
Model name
: 7534
Power source : DC3V.