Fujitsu AG G12LVCA Series Service Instruction page 40

Hide thumbs Also See for AG G12LVCA Series:
Table of Contents

Advertisement

For AO*G14LVLA
Trouble shooting 10-2
OUTDOOR UNIT Error Method:
INDOOR UNIT
Active filter error
Detective Actuators:
Outdoor unit Main PCB
Active filter module
Forecast of Cause :
1. External cause
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
OK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 3 : Check Active filter module
Check Active filter module. (PARTS INFORMATION 6)
>>If Active filter module is abnormal, replace it.
OK
OK
Check Point 4 : Replace Main PCB
If Check Point 1 - 3 do not improve the symptom, change Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When inverter input DC voltage is higher than 425V or
lower than 80V.
When a momentary power cut off occurred on low voltage
2. Connector connection failure
in the power supply circuit.
3. Main PCB failure 4. Active filter module failure
02-15