To inspect blower wheel, shine a flashlight into draft hood open-
ing. If cleaning is required, remove motor and wheel as follows:
1.
Remove the screw at the base of the burner partition panel
(see Fig. 52) and slide out the panel.
2.
Remove the 7 screws attaching the induced-draft motor
housing to the vestibule plate. (See Fig. 50.)
3.
The blower wheel can be cleaned at this point. If addi-
tional cleaning is required, continue with Steps 4 and 5.
4.
Remove the blower from the motor shaft by removing
2 setscrews.
5.
Removing motor: remove the 4 screws holding the motor
to the mounting plate. Remove the motor cooling fan by
removing one setscrew. Remove nuts that hold the motor
to the mounting plate.
6.
Reverse the procedure outlined above to reinstall the motor.

Burners and Igniters

CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this CAUTION can result in premature wear
and damage to equipment.
When working on gas train, do not hit or plug orifice spuds.
MAIN BURNERS
To access burners, remove burner access panel and slide out burn-
er partition. At the beginning of each heating season, inspect for
deterioration or blockage due to corrosion or other causes. Ob-
serve the main burner flames and adjust, if necessary.
Regulator
Gasket
Regulator
Baffle Assembly
(Low NO x Only)
Retainer
Inducer Fan-Motor Assembly
Burner Assembly
Fig. 50 — Heat Exchanger Assembly
Heater Tube
Assembly
Seal Strips,
Sponge Rubber
Flue Baffle
(Low NO x Only)
Orifice projection
Refer to Fig. 51 for maximum projection dimension for orifice
face to manifold tube.
1.00 in.
(25.4 mm)
Manifold
Pipe
Fig. 51 — Orifice Projection
REMOVAL AND REPLACEMENT OF GAS TRAIN
See Fig. 46, 50, 52, and 53.
1.
Shut off manual gas valve.
2.
Shut off power to unit.
3.
Remove the control box access panel.
4.
Remove the control box high voltage cover.
5.
Remove the screw at the base of the burner partition panel
(see Fig. 52) and slide out the panel.
6.
Disconnect gas piping at unit gas valve.
7.
Remove wires connected to gas valve. Mark each wire.
8.
Remove igniter wires and sensor wires at the Integrated
Gas Unit Controller (IGC). (See Fig. 54.)
9.
Remove the 2 screws attaching the burner rack to the ves-
tibule plate (see Fig. 50).
10. Slide the burner tray out of the unit (see Fig. 53).
11. Reverse the procedures outlined above to reinstall the
burner rack.