9. HEATER CONTROL
9.1. Control Specifications And Function Setting
• Table 1 shows the mode setting for the field-installed heater.
Table. 1 [Function Table]
Select unit numbers 01 to 03 or all units (AL [wired remote controller] / 07 [IR wireless remote controller])
Mode (function ) No.
Wired remote controller
Factory Setting
(RF thermostat)
11 (111)
23 (123)
1
1
2
1
2
2
*1 Heater will not operate during all error modes. Heater will only operate during a communication error between indoor unit and
outdoor unit.
• Table 2 shows how the field-installed heater is controlled.
Table. 2 [Heater Control Table]
(To -T RA ) >
Mode Change
2.7 ° F
[1.5 °C]
W1 ON
○
W2 ON
W1 OFF
W2 OFF
KEY
• W1: Furnace Heat Stage 1
• W2: Furnace Heat Stage 2
• To: Set point temperature
• T RA : Return Air temperature
• X: Time delay (Selectable. Default is 24 min. Selectable to 24 or 29 min)
Specifications are subject to change without notice.
NTXAMT12, 18, 24, 30, 36A112AA
Mode
●
Heater Available
─
Disable heater during
Defrost and Error
Heater Available
─
Enable heater and fan
during Defrost and
Error *1
T RA has not
W1 ON for
increased by
AND
0.9 °F [0.5°
> 7 min
C] in X min
○
AND
○
30
Heater Operation In
Heater Operation
Error
During Defrost
Heater Available
OFF
OFF
ON
ON
Condition
(To -T RA ) >
AND
2.7 ° F
AND
[1.5 ° C]
○
AND
AND