9. HEATER CONTROL

9.1. Control Specifications And Function Setting

• Table 1 shows the mode setting for the field-installed heater.
Table. 1 [Function Table]
Select unit numbers 01 to 03 or all units (AL [wired remote controller] / 07 [IR wireless remote controller])
Mode (function ) No.
Wired remote controller
Factory Setting
(RF thermostat)
11 (111)
23 (123)
1
1
2
1
2
2
*1 Heater will not operate during all error modes. Heater will only operate during a communication error between indoor unit and
outdoor unit.
• Table 2 shows how the field-installed heater is controlled.
Table. 2 [Heater Control Table]
(To -T RA ) >
Mode Change
2.7 ° F
[1.5 °C]
W1 ON
W2 ON
W1 OFF
W2 OFF
KEY
• W1: Furnace Heat Stage 1
• W2: Furnace Heat Stage 2
• To: Set point temperature
• T RA : Return Air temperature
• X: Time delay (Selectable. Default is 24 min. Selectable to 24 or 29 min)
Specifications are subject to change without notice.
NTXAMT12, 18, 24, 30, 36A112AA
Mode
Heater Available
Disable heater during
Defrost and Error
Heater Available
Enable heater and fan
during Defrost and
Error *1
T RA has not
W1 ON for
increased by
AND
0.9 °F [0.5°
> 7 min
C] in X min
AND
30
Heater Operation In
Heater Operation
Error
During Defrost
Heater Available
OFF
OFF
ON
ON
Condition
(To -T RA ) >
AND
2.7 ° F
AND
[1.5 ° C]
AND
AND
© 2022 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Fan Control When
Heater ON
High
High
T RA has not
(To -T RA ) <
increased by 0.9 °
0.9 °F
F [0.5° C] in 7 min
[0.5° C]