Bond in accordance with
applicable codes.
3. Make the Electrical Connections – USA and Mexico
WARNING: Risk of electric shock. Make sure the power has been disconnected before performing
the following procedures.
WARNING: Risk of electric shock. Connect the pump motor, in-line heater (if included), and
blower to properly grounded, grounding-type receptacles protected by Ground-Fault
Circuit-Interrupters (GFCI's) or Residual Current Devices (RCD's). Do not remove the grounding
pins from the plugs. Do not use grounding adapters.
NOTICE: The pump motor, in-line heater (if included), and blower are equipped with cords and plugs. A
qualified electrician must install a dedicated GFCI- or RCD-protected, 120 V, 15 A, grounded outlet for
each device. No other load should be on these circuits.
NOTE: A label identifying the model number and electrical rating of the product is located near the
whirlpool pump.
Install electrical outlets behind the bath, at least 1-1/2" (38 mm) above the subfloor, and within
reach of the 24" (610 mm) power cords.
Plug the pump motor, blower, and in-line heater (if included) into these outlets.
NOTE: Make sure the air actuator tubing is securely attached to the pump, and is not kinked or
damaged.
Kohler Co.
Heater
Pump
Blower
24" (610 mm) Maximum
Cord Length
7
GFCI-Protected
120 V, 15 A
Grounded Outlet
1208027-2-F