Samsung AC024BXUPCH/AA Technical Data Book page 53

Table of Contents

Advertisement

11. Installation
Outdoor Units
Connecting the refrigerant pipe
Maximum allowable pipe length [ft(m)]
Model Name
2Ton
AC024BXUPCH
3Ton (single fan)
AC036BXUDCH
3Ton (dual fan)
AC036BXUPCH
4Ton
AC048BXUPCH
5Ton
AC060BXUPCH
Recommended liquid and gas pipe diameters [inch(mm)]
Model Name
2Ton
AC024BXUPCH
3 Ton (single fan)
AC036BXUDCH
3 Ton (dual fan)
AC036BXUPCH
4Ton
AC048BXUPCH
5Ton
AC060BXUPCH
Max pipe length (L1)
Max pipe height difference between outdoor and indoor unit (h1)
98 (30)
164 (50)
164 (50)
164 (50)
98 (30)
Liquid Pipe Diameter
Φ3/8 (9.52)
Φ3/8 (9.52)
Φ3/8 (9.52)
Φ3/8 (9.52)
Φ3/8 (9.52)
49 (15)
98 (30)
98 (30)
98 (30)
49 (15)
Gas Pipe Diameter
Rated
Min
Φ3/4 (19.05)
Φ5/8 (15.88)
Φ3/4 (19.05)
Φ5/8 (15.88)
Φ7/8 (22.23)
Φ3/4 (19.05)
Φ7/8 (22.23)
Φ3/4 (19.05)
Φ7/8 (22.23)
Φ3/4 (19.05)
Max
Φ7/8 (22.23)
Φ7/8 (22.23)
Φ1-1/8 (28.58)
Φ1-1/8 (28.58)
Φ1-1/8 (28.58)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents