11. Installation
Outdoor Units
Main power terminal block specifications
Main power cable specifications
The power cable is not supplied with air conditioner.
Ensure the power wiring is sizing and specifications comply with all national, state, and local codes and
regulations.
Model
Power Source
Outdoor
AC024BXUPCH
AC036BXUDCH
208 - 230 V
AC036BXUPCH
60 Hz
AC048BXUPCH
AC060BXUPCH
• Outdoor units are installed using different power sources from that of indoor units, and this installation
manual only provides the MCA/MOP values for outdoor units.
For the MCA/MOP values for indoor units, refer to the installation manual for the indoor unit installed.
• RLA is based on AHRI 210/240 cooling standard condition [Indoor temp. : 26.7 °C / 80 °F(DB) / 19.46 °C /
67 °F(WB), Outdoor temp. : 35 °C / 95 °F(DB)]
• Voltage tolerance is ± 10 %.
• Maximum allowable voltage between legs is 2%.
RLA (A)
FAN1(A)
17.6
1.25
17.8
1.25
17.8
1.25
23.5
1.25
23.9
1.25
MOC
MCA (A)
FAN2(A)
-
-
1.25
1.25
1.25
[Unit : inch(mm)]
MOP (A)
24.1
30
24.4
35
25.6
35
32.7
40
33.2
40