4. SERVICE PROCEDURES

4-2 Checking the Electrical Components

(1)
Measurement of Insulation
Resistance
• The insulation is in good condition if the
resistance exceeds 1 MΩ.
1
Power Supply Wires
Clamp the earthed wire of the Power Supply
wires with a lead clip of the insulation resis-
tance tester and measure the resistance by
placing a probe on either of the power wires.
(Fig. 39)
Then measure the resistance between the earthed
wire and the other power wire. (Fig. 39)
2
Indoor Unit
Clamp an aluminum plate fin or copper tube
with the lead clip of the insulation resistance
tester and measure the resistance by placing
a probe on high voltage terminal on the
terminal plate (Fig. 40)
See Fig. 28.
3
Outdoor Unit (AE425SHE)
Clamp a metallic part of the unit with the lead
clip of the insulation resistance tester and
measure the resistance by placing a probe on
1 and then 2 on the 8 or 6P terminal plate.
(Fig. 40)
See Fig. 28.
3
Outdoor Unit (AE425SH3E,
AE436SH3E, AE448SH3E)
Clamp a metallic part of the unit with the lead
clip of the insulation resistance tester and
measure the resistance by placing a probe on
5 and then 6, and then 7 on the 8P terminal
plate. (Fig. 40)
See Fig. 29.
Clip
Probe
Clip
Copper
tube or
metallic part
96
Earthed wire
Insulation
tester
0638_X_S
Fig. 39
Terminal plate
Probe
Insulation
tester
0639_X_S
Fig. 40