7.8
Gas combustion checks
CO
2
It is better to set the burner with CO
3
Pci 8600 kcal/m
).
This way avoiding a loss of calibration setting (for example draft
variation) that could cause combustion with little air and the pro-
duction of CO.
7.9
Burner operation
NORMAL FIRING
(n° = seconds from instant 0)
NO FIRING
Key Fig. 41 - Fig. 42
1
Thermostat
2
Motor
3
Air gate valve
4
Ignition transformer
5
First valve
6
First flame
7
Second valve
8
Second flame
9
Lock-out
Start-up, calibration and operation of the burner
not higer than 10% (gas with
2
Fig. 41
Fig. 42
CO
It must be not higher than 100 mg/kWh.
7.9.1
Burner flame goes out during operation
If the flame should accidentally go out during operation, the burn-
er will lock out within 1s.
D3202
D3203
31
GB
20035573