Mitsubishi Electric PLA-ZRP35BAR1.UK Service Manual page 31

Table of Contents

Advertisement

9-6-1. Thermistor
<Thermistor Characteristic Graph>
Thermistor for
lower temperature
Thermistor R
=15k" ± 3%
0
Fixed number of B=3480 ± 2%
1
Rt=15exp { 3480(
273+t
0:
15 k"
10:
9.6 k"
20:
6.3 k"
25:
5.4 k"
30:
4.3 k"
40:
3.0 k"
9-6-2. DC Fan motor (FAN MOTOR/INDOOR CONTROLLER BOARD)
Check method of DC fan motor (fan motor / indoor controller circuit board)
Notes
1
· High voltage is applied to the connector (CNMF) for the fan motor. Pay attention to the service.
· Do not pull out the connector (CNMF) for the motor with the power supply on.
(It causes trouble of the indoor controller circuit
Self check
2
Symptom : The indoor fan cannot turn around.
Indoor controller board fuse check
Is the fuse normal?
Yes
Wiring contact check
Contact of fan motor connector (CNMF)
Is there contact failure?
No
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit
TEST POINT
1 : V
DC
TEST POINT
2 : V
CC
Is the voltage normal?
No
Replace indoor
controller board
Check the operation.
NG
Replace the fan motor.
OCH535A
Room temperature thermistor (TH1)
Pipe temperature thermistor/liquid (TH2)
Condenser/evaporator temperature
thermistor (TH5)
1
) }
273
Is the resistance
between the terminals of
drain pump normal?
Replace the drain pump.
Yes
Wiring recovery
board.
(between 1 (+) and 4 (-) of the fan connector): V
(between 5 (+) and 4 (-) of the fan connector): V
Yes
Replace indoor controller board.
OK
END
board and fan motor.)
No
310–340 V DC
DC
15 V DC
CC
Replace the fan motor.
Check the operation of fan.
NG
31
< Thermistor for lower temperature >
50
40
30
20
10
0
-20 -10 0
10 20 30 40 50
Temperature (:)
Replace the fan motor.
Replace the indoor controller board.
OK
END