Download Print this page

Airflow Specifications - Goodman GMVC95 Manual

Multi-position, two-stage/variable-speed gas furnace
Hide thumbs Also See for GMVC95:

Advertisement

p
s
roduct
peciFications
gMVc95 a
s
irFlow
peciFications
H
-
s
-s
c
igH
or
ingle
tage
ooling
GMVC950453BXAA
Cooling
Adjust
CFM
1
Speed Tap
Tap
Minus (-)
585
A
Normal
650
Plus (+)
715
Minus (-)
810
B
Normal
900
Plus (+)
990
Minus (-)
990
C
Normal
1100
Plus (+)
1210
Minus (-)
1080
D
Normal
1200
Plus (+)
1320
¹
@ .1" to .8" W.C. ESP
Notes:
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
Do not operate above .5" w.c. ESP in heating mode. Operating CFM between .5" and .8" w.c. is tabulated for cooling purposes only.
l
-s
c
s
ow
tage
ooling
peeds
GMVC950453BXAA
Cooling
Adjust
CFM
1
Speed Tap
Tap
Minus (-)
390
A
Normal
435
Plus (+)
480
Minus (-)
545
B
Normal
605
Plus (+)
665
Minus (-)
665
C
Normal
735
Plus (+)
810
Minus (-)
725
D
Normal
805
Plus (+)
885
¹
@ .1" to .8" W.C. ESP
Notes:
All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
For most jobs, about 400 CFM per ton when cooling is desirable.
Do not operate above .5" w.c. ESP in heating mode. Operating CFM between .5" and .8" w.c. is tabulated for cooling purposes only.
6
s
peeds
GMVC950704CXAA
Cooling
Adjust
CFM
1
Speed Tap
Tap
Minus (-)
585
A
Normal
650
Plus (+)
715
Minus (-)
810
B
Normal
900
Plus (+)
990
Minus (-)
1195
C
Normal
1325
Plus (+)
1460
Minus (-)
1440
D
Normal
1600
Plus (+)
1760
GMVC950704CXAA
Cooling
Adjust
CFM
1
Speed Tap
Tap
Minus (-)
390
A
Normal
435
Plus (+)
480
Minus (-)
545
B
Normal
605
Plus (+)
665
Minus (-)
800
C
Normal
890
Plus (+)
975
Minus (-)
965
D
Normal
1070
Plus (+)
1180
www.goodmanmfg.com
GMVC950905DXAA
Cooling
Adjust
CFM
1
Speed Tap
Tap
Minus (-)
720
A
Normal
800
Plus (+)
880
Minus (-)
945
B
Normal
1050
Plus (+)
1155
Minus (-)
1305
C
Normal
1450
Plus (+)
1595
Minus (-)
1800
D
Normal
2000
Plus (+)
2200
GMVC950905DXAA
Cooling
Adjust
CFM
1
Speed Tap
Tap
Minus (-)
480
A
Normal
535
Plus (+)
590
Minus (-)
635
B
Normal
705
Plus (+)
775
Minus (-)
875
C
Normal
970
Plus (+)
1070
Minus (-)
1205
D
Normal
1340
Plus (+)
1475
GMVC951155DXAA
Cooling
Adjust
CFM
1
Speed Tap
Tap
Minus (-)
720
A
Normal
800
Plus (+)
880
Minus (-)
945
B
Normal
1050
Plus (+)
1155
Minus (-)
1305
C
Normal
1450
Plus (+)
1595
Minus (-)
1800
D
Normal
2000
Plus (+)
2200
GMVC951155DXAA
Cooling
Adjust
CFM
1
Speed Tap
Tap
Minus (-)
480
A
Normal
535
Plus (+)
590
Minus (-)
635
B
Normal
705
Plus (+)
775
Minus (-)
875
C
Normal
970
Plus (+)
1070
Minus (-)
1205
D
Normal
1340
Plus (+)
1475
SS-GMVC95

Hide quick links:

Advertisement

loading