16. If the DHCP protocol is disabled on the battery management
system and the IP address is specified, set the IP address of the
battery management system to 192.168.12.130 during
commissioning of the inverter.
17. If the DHCP protocol is enabled on the battery management
system and the IP address is variable, do not make any changes
to the configuration of the battery communication during
commissioning of the inverter. The default battery communication
settings will be automatically used.
18. Activate the next menu item. To do this, tap with the fingers on the highlighted area beside the display.
☑ The battery management system display on the primary battery cabinet changes from the Status to INIT
mode.
☑ The SWITCH control element flashes.
19. Commission the inverter.
☑ Once commissioning of the inverter is complete, the battery management system display on the primary
battery cabinet changes from the Status to PRECH mode. This indicates that precharging mode of the
battery has started.
☑ Precharging mode is complete once the battery management system display on the primary battery cabinet
changes from the Status to OK mode. The battery is now ready for operation.
Also see:
• Checking the Mounting and Connection Work ⇒ page 89
• Design of the Battery Cabinet ⇒ page 36
• Connection Area of the Battery Management System ⇒ page 75
• Commissioning the Inverter ⇒ page 90
• Safety when Commissioning the Battery ⇒ page 92
• Wiring of the Battery Modules ⇒ page 78
• Overview of the CAN Communication System ⇒ page 81
• Battery Event Messages ⇒ page 152
9.5

Configuring the Temperature and Humidity Sensor

1. Commission the temperature and air humidity sensor (see manual for the temperature and humidity sensor).
2. Set the sampling rate for the ambient temperature and humidity measurement to 120 s.
3. Start the temperature sensor recording. To do this, press and hold the LOGGER button on the temperature sensor
for more than 2 seconds.
4. Check that the message DATALOGGER appears on the temperature sensor display. This indicates that the
temperature sensor has started recording.
5. If the message DATALOGGER does not appear on the temperature sensor display, start the temperature sensor
recording again.
9.6
Registration in Sunny Portal
9.6.1

Profiles for data communication

Different profiles are available to control the intensity of data communication in the system.