Remove 5 screws if necessary
(either side of cabinet)
FIGURE 27
C-Supply Air Blower
1 - Check and clean blower wheel.
2 - Motors used on the Lennox EL180UHE(X) series units
are permanently lubricated and need no further lu
brication.
D-Flue and Chimney
Flue must conform to local codes. In the absence of local
codes, flue must meet the National Fuel Gas Code
ANSI-Z223.1 venting requirements. Flue pipe deteriorates
from the inside out and must be disconnected in order to
check thoroughly. Check flue pipe, chimney and all con
nections for tightness and to make sure there is no block
1
age or leaks.
2
E-Electrical
3
1 - Check all wiring for loose connections.
4
2 - Check for the correct voltage at the furnace (furnace
5
3 - Check amp-draw using a true RMS meter on the blow
Page 27
operating). Correct voltage is 120VAC + 10%
er motor with blower access panel in place. See figure
28.
Furnace Nameplate__________Actual__________
Check Motor AMP Draw
OFF
EX −
P
MR
W
3
2
1
kWh
kVAr
V1 V2
COM
M
V3
True RMS Meter
FIGURE 28