EL180UHE BURNER, COMBUSTION AIR INDUCER ASSEMBLY
Flue Transition
Rollout Switches
(-090, -110 -135
units)
Rollout Switches
(-045 and -070 units)
Flame
Sensor
16 -Reinstall burner box and manifold assembly.
17 -Reconnect all wires.
18 -Reconnect top cap and vent pipe to combustion air in
ducer outlet.
19 -Reconnect gas supply piping.
20 -Turn on power and gas supply to unit.
21 -Set thermostat and check for proper operation.
22 -Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred
means.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly af
ter leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.
23 -If a leak is detected, shut gas and electricity off and re
pair leak.
24 -Repeat steps 24 and 26 until no leaks are detected.
HEAT EXCHANGER REMOVAL
Pressure Switch
Ignitor
Combustion Air Inducer
Manifold And Gas Valve
FIGURE 25
&
Gasket
Orifice Plate
Collector Box
25 -Replace access panel.
EL180UHE NOx INSERTS
NOx Insert
Page 26
Heat Exchanger
Retention Rings
Cross Over
FIGURE 26