Mounting the indoor unit
5.2.1
To install the mounting plate
1 Install the mounting plate temporarily.
2 Level the mounting plate.
a
117
d
a
e
48
162
a
Recommended mounting plate fixing spots
b
Pocket for the pipe port cover
c
Tabs for placing a spirit level
d
Through-the-wall hole Ø65 mm
5.2.2
To drill a wall hole
CAUTION
For walls containing a metal frame or a metal board, use a
wall embedded pipe and wall cover in the feed-through
hole to prevent possible heat, electrical shock, or fire.
NOTICE
Be sure to seal the gaps around the pipes with sealing
material (field supply), in order to prevent water leakage.
1 Bore a 65 mm large feed-through hole in the wall with a
downward slope towards the outside.
2 Insert a wall embedded pipe into the hole.
3 Insert a wall cover into the wall pipe.
a b
c
a
Wall embedded pipe
b
Putty
c
Wall hole cover
4 After completing wiring, refrigerant piping and drain piping, do
NOT forget to seal the gap with putty.
FTXTP-M_FTXTP-N
Daikin room air conditioner
3P650253-16U – 2023.03
≥50
(mm)
c
b
c
a
211
h
g
a
231
337
770
3 Mark the centres of the drilling points on the wall using a tape
measure. Position the end of tape measure at symbol " ".
4 Finish the installation by securing the mounting plate on the wall
using M4×25L screws (field supply).
INFORMATION
The removed pipe port cover can be kept in the mounting
plate pocket.
a
116
237
d
f
A
a
a
171
48
337
f
Position for the tape measure at symbol " "
g
Gas pipe end
h
Liquid pipe end
e
Drain hose position
5.2.3
To remove the pipe port cover
INFORMATION
To connect the piping on right-side, right-bottom, left-side
or left-bottom, the pipe port cover MUST be removed.
1 Cut off the pipe port cover from inside the front grille using a
coping saw.
2 Remove any burrs along the cut section using a half round
needle file.
5 Unit installation