6-4. STANDARD OPERATION DATA
Service Ref.
Mode
Capacity
Input
Indoor unit Service Ref.
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase, Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
The unit of pressure has been changed to Mpa based on international SI system.
The conversion factor is :
Cooling
W
4,400
kW
1.65
V
A
0.29
1.6V
1, 50
V
240
A
7.66
MPa
1.99
(kgf/F)
(20.3)
MPa
0.49
(kgf/F)
(5.0)
°C
75
°C
46
°C
5.0
m
5
°C
D.B.
27
°C
W.B.
19
°C
D.B.
12.4
°C
D.B.
35
°C
W.B.
24
0.70
0.15
f )
1(Mpa)=10.2(kgf/f
PMH-P1.6BA
Heating
5,000
1.70
PMH-P1.6BA
1, 50
240
0.29
PUH-P • GA
1.6Y
1.6V
1.6Y
3, 50
1, 50
3, 50
415
240
415
2.67
8.19
2.86
2.15
(21.9)
0.41
(4.2)
80
50
1.2
5
20
15
47.2
7
6
—
—
26
PMH-P2BA
Cooling
Heating
5,400
6,250
2.35
PMH-P2BA
1, 50
240
0.29
PUH-P • GA
2V
2Y
2V
1, 50
3, 50
1, 50
240
415
240
11.11
3.88
11.51
2.37
(24.2)
(25.7)
0.49
(5.0)
(4.2)
86
53
5.0
5
27
19
11.4
35
24
0.67
0.15
2.42
0.29
2Y
3, 50
415
4.02
2.52
0.41
93
53
1.0
5
20
15
49.0
7
6
—
—