Fujitsu ASYA07LBCM Service Manual page 53

Table of Contents

Advertisement

Trouble shooting 28
No Operation (Power is ON)
Check Point 1 : Check indoor and outdoor installation condition
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control, or terminals between Indoor Units.
Or, check if there is an open cable connection.
Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and
Data & Technical Manual.
OK
Turn off Power and check/ correct followings.
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
OK
Check Point 2 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
OK
Check Point 3 : Check Electrical Components at Indoor and Outdoor
Check Voltage at CN17 of Controller PCB. (Power supply to Remote Control)
>> If it is DC12V, Remote Control(Option) is failure. (Controller PCB is normal)
>> If it is DC 0V, Controller PCB is failure.
>> If the symptom does not change by above Check 1, 2, 3, replace Inverter PCB of Outdoor unit.
Forecast of Cause:
1. Setting/ Connection failure 2. External cause
3. Electrical Component defective
(Check Remote Control once again) >> Replace Controller PCB
02-31
>> Replace Remote Control(Option)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Asya09lbcmAsya12lbcmAoya14lac2

Table of Contents