Capacity –
F1B
Power supply
6 kW 3N~ 400 V
9 kW 3N~ 400 V
L1 L2
Q3DI
L1
L2
L3
3N~ , 50 Hz
400 V AC
3 Fix the cable with cable ties to the cable tie mountings.
During connection of the backup heater, miswiring is possible. To
detect possible miswiring, it is highly recommended to measure the
resistance value of the heater elements. Depending on the capacity
and power supply, following resistance values (see table below)
should be measured. ALWAYS measure the resistance on the
contactor clamps K1M, K2M, and K5M.
3 kW
1N~ 230 V
1N~ 230 V
K1M/1 K5M/13
52.9Ω
K1M/3
K1M/5
K1M/3 K1M/5
26.5Ω
K2M/1 K5M/13
K2M/3
K2M/5
K2M/3 K2M/5
52.9Ω
K1M/5 K2M/1
Example measure resistance between K1M/1 and K5M/13:
K1M
1 3 5 13
2 4 6 14
Ω
Ω
K5M
1 3 5 13
2 4 6 14
To connect the backup heater kit to the outdoor unit
The wiring between the backup heater kit and the outdoor unit is as
follows:
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688014-1D – 2022.10
X14M
F1B
X14M
1 2 3 4 5 6
L3
N
N
6 kW
6 kW
9 kW
3N~ 400 V
3N~ 400 V
52.9Ω
105.8Ω
105.8Ω
105.8Ω
158.7Ω
105.8Ω
105.8Ω
52.9Ω
105.8Ω
105.8Ω
26.5Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
52.9Ω
132.3Ω
K2M
K2M
1 3 5 13
2 4 6 14
A
X3M
1
2
3
4
5
B
X15M
6
7
8
9 10
X15M
HV
EKLBUHCB6W
A
Outdoor unit
B
Backup heater kit
HV
High voltage connections (backup heater thermal
protector + backup heater connection)
LV
Low voltage connection (backup heater thermistor)
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
1 On the backup heater kit, connect the LV and HV cables to the
appropriate terminals as shown in the illustration below.
F1B
X15M
1
2
7 6
9 8
10
LV
HV
2 On the outdoor unit, connect the HV cable to the appropriate
terminals as shown in the illustration below.
180°
3 On the outdoor unit, connect the LV cable to the appropriate
terminals as shown in the illustration below.
6 Electrical installation
X5M
1
2
1
2
LV
HV
6 7 8 9 10
X15M
EKLBUHCB6W
X3M
1 2 3 4 5
X3M
Installation manual