Sprin kler 14 d
Nom i nal
Thread Size
Or i fice
N.P.T.
B.S.P.
Inches mm
1/2"
15 mm
1/2
15
1/2"
15 mm
1/2
15
--
10 mm
3/8
10
--
10 mm
3/8
10
Nom i nal
Thread Size
Or i fice
N.P.T.
B.S.P.
Inches mm
1/2"
15 mm
1/2
15
1/2"
15 mm
1/2
15
--
10 mm
3/8
10
--
10 mm
3/8
10
Ap proved Tem per a tures
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C),
200 °F (93 °C), 286 °F (141°C), and 360 °F (182 °C)
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and
200 °F (93 °C)
1
Base part num ber is shown. For com plete part num ber, see Vi king's cur rent price sched ule.
2
This ta ble shows the list ings and ap prov als avail able at the time of print ing. Other ap prov als are in pro cess. Check with the man u fac turer for
any additonal ap prov als.
3
Ac cep tance for use, City of New York Board of Stan dards and Ap peals, is pend ing.
4
UL and ULC Listed for Light Haz ard oc cu pan cies. Lo cate hor i zon tal side wall sprin klers with de flec tors 4" to 12"(102 mm to 304 mm) be low
ceil ings, and 4" to 6" (102 mm to 152 mm) from walls. Align top of hor i zon tal side wall de flec tors par al lel to the ceil ing or roof.
Ex cep tion: Hor i zon tal side wall sprin klers may be in stalled with the de flec tors less than 4" (102 mm) from the wall in which they are in stalled.
Viking ver ti cal side wall sprin klers may be in stalled pen dent or up right. Lo cate ver ti cal side wall sprin klers with de flec tors 4" to 6" (102 mm to
152 mm) from walls and 4" to 6" (102 mm to 152 mm) be low ceil ings.
Exception: Pen dent ver ti cal side wall sprin klers may be lo cated with the de flec tors less than 4" (102 mm) be low the ceil ing in which they are in
stalled.
5
UL and ULC Listed as cor ro sion-resistant sprin klers.
6
Met ric K-Factor shown is for use when pres sure is mea sured in kPa. When pres sure is mea sured in BAR, mul ti ply the met ric K-Factor shown
by 10.0.
D. When re plac ing ex ist ing sprin klers,
the sys tem must be re moved from
ser vice. Re fer to the ap pro pri ate sys -
tem de scrip tion and/or valve in struc -
tions. Prior to re mov ing the sys tem
from ser vice, no tify all Au thor ities
Hav ing Ju ris dic tion. Con sid er ation
should be given to em ploy ment of a
fire pa trol in the af fected area.
1. Re move the sys tem from ser vice,
drain all wa ter, and re lieve all
pres sure on the pip ing.
Re places sprin kler page 14 a-d, dated August 3, 1998
(added Part Num bers 09126 and 09127).
TECH NI CAL DATA
Ap proval Chart
®
Micromatic
Model M Side wall Sprin kler
5 mm Glass Bulb, Stan dard Re sponse
Re cessed with Vi king Model E-1 Re cessed Es cutch eon
Stan dard Or i fice
De scrip tion
1
Style
Base P/N
Horizontal
10224
Ver ti cal U/P
10226
Small Or i fice
Horizontal
09126
Ver ti cal U/P
09127
In stalled with Vi king Model F-1 Ad just able Es cutch eon
Stan dard Or i fice
De scrip tion
1
Style
Base P/N
Horizontal
10224
Ver ti cal U/P
10226
Small Or i fice
Horizontal
09126
Ver ti cal U/P
09127
Footnotes
Ta ble 3
2. Using the al sprin kler wrench, re -
move the old sprin kler and in stall
the new unit. Care must be taken
to en sure that the re place ment
sprin kler is the proper model and
style, and has the ap pro pri ate or i -
fice size, tem per a ture rat ing, and
re sponse char ac ter is tics. A fully
stocked spare sprin kler cab i net
should be pro vided for this pur -
pose.
Nom i nal
Over all Length
6
K-factor
U.S. met ric Inches
mm
5.5
7,9
2.5
64
5.5
7,9
2.3
58
--
5,8
2.437
61,9
--
5,8
2.188
55,58
Nom i nal
Over all Length
6
K-factor
U.S. met ric Inches
mm
5.5
7,9
2.5
64
5.5
7,9
2.3
58
--
5,8
2.437
61,9
--
5,8
2.188
55,58
Ap proved Fin ishes
1 - Brass, Bright Brass, Chrome-Enloy
5
Polyester
, and Black Tef lon
2 - Wax-Coated Brass and Wax over Poly es ter (cor ro sion re sis tant)
April 29, 1999
MICROMATIC
MODEL M SIDE WALL
SPRIN KLERS
KEY
See Row A
See Row 1
of Approved
of Approved
A1
Temp. Chart
Finish Chart
List ings and Ap provals
4
4
3,4
UL
ULC
NYC
B1, B2
B1, B2
B1, B2
B1, B2
--
--
--
--
--
--
--
--
List ings and Ap provals
4
4
3,4
UL
ULC
NYC
A1, B2
B1, B2
B1, B2
A1, B2
--
--
--
--
--
--
--
--
®
5
, White Poly es ter
, Black
®5
3. Place the sys tem back in ser vice
and se cure all valves. Check and
re pair all leaks.
E. Sprin kler sys tems that have been
sub jected to a fire must be re turned
to ser vice as soon as pos si ble. The
en tire sys tem must be in spected for
dam age, and re paired or re placed as
nec es sary. Sprin klers that have been
ex posed to cor ro sive prod ucts of
com bus tion of high am bi ent tem per -
a tures, but have not op er ated, should
be re placed. Re fer to the Au thor ity
Hav ing Ju ris dic tion for min i mum re -
place ment re quire ments.
Form No. F_072198
®
2
LPCB
--
--
--
--
2