Sprin kler 14 b
Screw: Brass UNS-C36000
Pip Cap:
For Part Num ber 10224: Bronze
UNS-C31600
For all oth ers: Cop per UNS-C11000
and Stain less Steel UNS-S30400
Poly es ter Coated Sprin klers:
Spring: Nickel Al loy, ex posed
Screw: Brass UNS-C36000
Painted white for ap pear ance only.
Pip Cap:
For Part Num ber 10224: Bronze
UNS-C31600
For all oth ers: Cop per UNS-C11000
and Stain less Steel UNS-S30400
Tef lon
®
Coated Sprin klers:
Screw: Brass UNS-C36000
Painted black for ap pear ance only.
Spring: Nickel Al loy, ex posed
Pip Cap: (Tef lon
coated)
®
For Part Num ber 10224: Bronze
UNS-C31600
For all oth ers: Cop per UNS-C11000
and Stain less Steel UNS-S30400
AC CES SORIES
Sprin kler Wrenches:
®
A. Stan dard Micromatic
Wrench:
Part No. 05000CW/B
Avail able since 1982.
B. Wrench for coated and re cessed
®
Micromatic
Sprin klers:
Part No. 07398W
Avail able since 1990.
Re fer to "Sprin kler Ac ces sories" sec tion
of the Vi king En gi neering and De sign
Data book for other ac ces so ries.
AVAIL ABLE FIN ISHES
Chrome-Enloy
®
, Brass, Bright Brass,
White Poly es ter, Black Poly es ter, Black
Tef lon
, and Wax-Coated Brass or Poly -
®
es ter
5. AVAILABILITY AND SERVICE
Vi king sprin klers are avail able through a
net work of do mes tic, Ca na dian, and in -
ter na tional dis trib u tors. See the Yel low
Pages of the tele phone di rec tory for a
lo cal dis trib u tor (listed un der "Sprin -
klers-Automatic-Fire") or con tact Vi king.
Vi king Tech ni cal Data may be found on
The Vi king Cor po ra tion's Web site at
http://www.vikingcorp.com.
The Web site may in clude a more re cent
edi tion of this Tech ni cal Data page.
6. GUARANTEES
For de tails of war ranty, re fer to Vi king's
cur rent list price sched ule or con tact The
Vi king Cor po ra tion di rectly.
TECH NI CAL DATA
7. INSTALLATION
WARNING: Vi king sprin klers are man u -
fac tured and tested to meet the rigid re -
quire ments of the ap prov ing agen cies.
The sprin klers are de signed to be in -
stalled in ac cor dance with rec og nized
in stal la tion stan dards. De vi a tion from
the stan dards or any al ter ation to the
sprin kler af ter it leaves the fac tory in -
clud ing, but not lim ited to: paint ing, plat -
ing, coat ing, or mod i fi ca tion, may ren der
the sprin kler in op er a tive and will au to -
mat i cally nul lify the ap prov als and any
guar an tee made by The Vi king Cor po ra -
tion. Re fer to the Au thor ity Hav ing Ju ris -
dic tion prior to in stal la tion.
A. Sprin klers are to be in stalled in ac cor -
dance with the lat est pub lished stan -
dards of the Na tional Fire Pro tec tion
As so ci a tion, Fac tory Mu tual, Loss
Pre ven tion Coun cil, Assemblee
P l e n i e r e ,
V e r b a n d
Sachversicherer or other sim i lar or -
ga ni za tions, and also with the pro vi -
sions of gov ern men tal codes, or di -
nances, and stan dards, when ever
ap pli ca ble.
B. Sprin klers must be han dled with care.
They must be stored in a cool, dry
place in their orig i nal ship ping con -
tainer. Never in stall sprin klers that
have been dropped, dam aged, or ex -
posed to tem per a tures in ex cess of
the max i mum am bi ent tem per a ture
al lowed. Never in stall any glass-bulb
sprin kler if the bulb is cracked or if
there is a loss of liq uid from the bulb.
If a glass bulb lacks the ap pro pri ate
amount of fluid, it should be set aside
and re turned to Vi king (or an au tho -
rized Vi king dis trib u tor) for anal y sis
as soon as pos si ble. If the sprin kler is
not re turned to Vi king, it should be
de stroyed im me di ately.
C. Cor ro sion-resistant sprin klers must
be in stalled when sub ject to cor ro -
sive at mo spheres. When in stall ing
cor ro sion-resistant sprin klers, take
care not to dam age the cor ro -
sion-resistant coat ing. Use only the
spe cial wrench de signed for in stall -
ing coated and re cessed Microfast
Sprin klers (any other wrench may
dam age the unit). DO NOT use the
sprin kler de flec tor to start or thread
the sprin kler into a fit ting.
D. Use care when lo cat ing sprin klers
near fix tures that can gen er ate heat.
Do not in stall sprin klers where they
will be ex posed to tem per a tures that
ex ceed the max i mum rec om mended
MICROMATIC
MODEL M SIDE WALL
SPRIN KLERS
am bi ent tem per a ture for the tem per -
a ture rat ing used.
E. Be fore in stal la tion, be sure to have
the ap pro pri ate sprin kler model and
style, with the proper or i fice size,
tem per a ture rat ing, and re sponse
char ac ter is tics. The sprin kler must
be in stalled af ter the pip ing is in place
to pre vent me chan i cal dam age.
1. In stall es cutch eon (if used), which
is de signed to thread onto the ex -
ter nal threads of the sprin kler. Re -
fer to the "Sprin kler Ac ces -
sories"section of the Vi king En gi -
neering and De sign Data book for
tech ni cal data de scrib ing ap -
proved es cutch eons and other ac -
ces so ries.
2. Ap ply a small amount of pipe-joint
com pound or tape to the ex ter nal
threads of the sprin kler only, tak -
ing care not to al low a build-up of
com pound in the sprin kler in let.
d e r
3. In stall the sprin kler on the pip ing
us ing the spe cial sprin kler wrench
only,
tak ing
over-tighten or dam age the sprin -
kler op er at ing parts. DO NOT use
the de flec tor to start or thread the
sprin kler into a fit ting.
F. Af ter in stal la tion, the en tire sprin kler
sys tem must be tested in ac cor dance
with the rec og nized in stal la tion stan -
dards. The test is ap plied af ter the
sprin kler in stal la tion to en sure that no
dam age has oc curred to the sprin kler
dur ing ship ping and in stal la tion, and
to make sure the sprin kler has been
prop erly tight ened. If a thread leak
oc curs, nor mally the sprin kler must
be re moved, new pipe-joint com -
pound or tape ap plied, and then re in -
stalled. This is due to the fact that
when the joint seal is dam aged, the
seal ing com pound or tape is washed
out of the joint. Air test ing the sprin -
kler pip ing prior to test ing with wa ter
may be con sid ered in ar eas where
leak age dur ing test ing must be pre -
vented. Re fer to the ap pro pri ate
tech ni cal data and the Au thor ity Hav -
ing Ju ris dic tion prior to air test ing the
sprin kler pip ing.
G. Sprin klers must be pro tected from
®
me chan i cal dam age. Wet-pipe sys -
tems must be pro vided with ad e -
quate heat. Do not in stall ver ti cal
side wall sprin klers in the pen dent po -
si tion on dry sys tems in ar eas sub ject
to freez ing. When in stall ing ver ti cal
side wall sprin klers on dry sys tems in
heated ar eas, re fer to the In stal la tion
Guides and the Au thor ity Hav ing Ju -
ris dic tion.
April 29, 1999
®