Combustion Air & Venting Requirements; General Information; Vent Termination - Trane VR104GD-U Series Installation Instructions Manual

Single package gas heating / electric cooling
Table of Contents

Advertisement

WARNING:
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for
each appliance connected to the venting system
being placed into operation could result in carbon
monoxide poisoning or death.
The following steps shall be followed with each
individual appliance connected to the venting
system being placed in operation, while all other
appliances connected to the venting system are
not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and
horizontal pitch, as required in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 or the CSA
B149.1, Natural Gas and Propane Installation
Codes and these instructions. Determine that
there is no blockage or restriction, leakage,
corrosion and other deficiencies which could
cause an unsafe condition.
3. As far as practical, close all building doors
and windows and all doors between the space
in which the appliance(s) connected to the
venting system are located and other spaces
of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not
connected to the venting system. Turn on
any exhaust fans, such as range hoods and
bathroom exhausts, so they are operating at
maximum speed. Do not operate a summer
exhaust fan.
6. Follow the lighting instructions. Place the
appliance being inspected into operation.
Adjust the thermostat so appliance is operating
continuously.
7. Test for spillage from draft hood equipped
appliances at the draft hood relief opening after
5 minutes of main burner operation. Use the
flame of a match or candle.
8. If improper venting is observed during any of
the above tests, the venting system must be
corrected in accordance with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 and/or CSA
B149.1, Natural Gas and Propane Installation
Codes.
9. After it has been determined that each appliance
connected to the venting system properly vents
when tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and
any other gas-fired burning appliance to their
previous conditions of use.
6
COMBUSTION AIR & VENTING REQUIREMENTS

General Information

WARNING:
Installation methods other than those described in
the following sections must comply with the National
Fuel Gas Code and all applicable local codes for
providing sufficient combustion air to the unit.
• Provisions must be made during the installation of this unit
that provide an adequate supply of air for combustion.
• Instructions for determining the adequacy of an installation
can be found in the current revision of the NFGC (ANSI
Z223.1 / NFPA54). Consult local codes for special
requirements. These requirements are for US installations
as found in the NFGC.
• The requirements in Canada (B149.1) are structured
differently. Consult with B149.1 and local code officials for
Canadian installations.
WARNING:
Combustible air must not be drawn from a
contaminated atmosphere. Excessive exposure to
contaminated combustion air will result in safety
and performance related problems.
• To maximize heat exchanger life, the combustion air
must be free of chemicals that can form corrosive acidic
compounds in the combustion gases. The recommended
source of combustion air is to use clean air from outside.
DO NOT place any chemicals with flammable or caustic
vapors or these other corrosive chemicals near the vent
termination:
• Gasoline/Kerosene
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents
• Cements, glues, paint removers, varnishes, etc.
• Hydrochloric acid
• Masonry acid washing materials
• Plumbing Stack

Vent Termination

This unit has been equipped with an integral venting system
and designed to operate only with this venting system. No
additional venting shall be used. This unit must be vented to
the outdoors.
WARNING:
This unit is intended for outdoor installation only.
Do not vent the unit through a conventional venting
system.
A vent cover assembly has been supplied with the unit. and
can be found secured to the gas controls within the control
area of this unit. The vent cover assembly must be installed
to assure proper operation of the unit.