Table 1
A
B
C
D
53-1/4
24
20
22
(2)
Make sure the range of the unit's external static pres-
sure is not exceeded. (up to 0.5 in.W.C. at "H" speed.)
(3)
Condensation may form on the product during COOL
operation. Be sure to provide (fi eld supplied) and
install a second drain pan.
If installed vertically
Second drain pan
If installed horizontally
Second drain pan
5
E
F
G
H
I
11-
19-
12
14-1/2
19-5/8
15/16
15/16
Drain piping
Drain piping
(4)
Check if the unit is horizontally level.
CAUTION
Make sure the unit is installed level using a level tube: four
sides. (One thing to watch out for in particular is if the unit is
installed so that the slope is not in the direction of the drain
piping, this might cause leaking.)
If installed vertically
Level
If installed horizontally
Level
(5)
Secure the unit fi rmly to prevent it from falling.
(6)
When the unit is installed in a hot and humid place, it
is recommended to use the following drain pan insu-
lation kit, which is an optional accessory.
Drain pan insulation Kit
Vertically
DPI 48-60/20
Regarding the attachment of the drain pan insulation kit,
refer to the installation manual provided with the kit.
Horizontally
DPIH 48-61
English