Daikin FTQ24PAVJU Installation Manual page 14

Hide thumbs Also See for FTQ24PAVJU:
Table of Contents

Advertisement

10-2
REMOTE CONTROL SETTING
Forced off and ON/OFF operation should be selected by select-
ing the SECOND CODE NO. as shown in the table Table 4.
Table 4
External ON/OFF input
Forced off
ON/OFF operation
* factory set
Input A of forced off and ON/OFF operation work as shown
in Table 5.
Table 5
Forced off
Input A "on" to force a stop
(remote controller reception
prohibited)
Input A "off" to allow remote
controller
10-3
SETTING THE FILTER SIGN DISPLAY INTERVAL
Explain the following to the customer if the fi lter dirt settings
have been changed.
The fi lter sign display time is set to 2500 hours (equivalent
to 1 year's use) when shipped.
The settings can be changed to not display.
When installing the unit in a dusty place, set the fi lter sign
display time to shorter intervals (1,250 hours).
Explain it to the customer that the fi lter needs to be cleaned
regularly to prevent clogging and also the time that is set.
Mode No.
FIRST CODE NO.
0
Displayed time
10 (20)
1 (low/high)
(units: hours)
3
Filter sign display
10-4
INSTALLATION OF THE OPTIONAL AIR FILTER
Purchase and install the air fi lter as in Table 6 .
Table 6
18 · 24 type
13
FIRST
SECOND
Mode No.
CODE NO.
CODE NO.
01*
12 (22)
1
02
ON/OFF operation
Unit operated by changing input
A from "off" to "on"
Unit stopped by changing input A
from "on" to "off"
SECOND
CODE NO.
01
02
Filter dirt
low
high
2500/
10000/
1250
5000
ON
OFF
Air fi lter
FIL 48-61
(1)
Take off the part on the bottom of the front panel.
(2)
Insert the air fi lter as far as it can go.
10-5
INSTALLATION OF THE ELECTRIC HEATER KIT
WARNING
All phases of the electrical installation must comply with
national, state, provincial, and local codes.
When connecting an electric heater, be sure to install an
earth leakage circuit breaker procured locally.
If an earth leakage circuit breaker is not installed, electric
shock or fi re may result.
Regarding the rated current of the earth leakage circuit
breaker to be installed, refer to the H.M.C.A. value indicated
on the manufacturer's label or in a technical document.
The recommended rapid sensitive current and tripping time
are indicated below.
Recommended specifi cations of circuit breaker
Rapid sensitive current
Tripping time
Air filter (optional accessories)
30mA
0.1sec
English