Flue Requirements - Rinnai Infinity 17i Installation And User Manual

Continuous flow water heater
Hide thumbs Also See for Infinity 17i:
Table of Contents

Advertisement

FLUE REQUIREMENTS - INSTALLING
The flue must be installed by a competent, authorised person. It is the installer's
responsibility to ensure that the unit has been installed to all current local require-
ments.
Ensure that the flue terminal and hot water outlet connection cannot be touched by
children. The flue must be clear of obstructions and shrubbery.
Flue Length.
0
The flue Total Equivalent Length is limited to 6.5m. Each 90
bend should be considered
0.5m of the Total Equivalent Length. The maximum number of bends is 3.
When the flue size is increased to 80/125mm the Total Equivalent Length can be ex-
tended to 10m, less 1m per bend, with a maximum of 3 bends.
When using the split flue, 80/80mm, the Total Equivalent Length of air intake can be ex-
tended to 5m with 1bend, the Total Equivalent Length of exhaust can be extended to
25m with a maximum of 3 bends.
The flue may terminate in a zone of a different pressure as the inlet, eg using a wall inlet
terminal, the outlet may be positioned on the roof using a roof exit terminal.
The exit may also be at an opposite or adjacent wall. In all cases the exit terminal should
be located in same or higher elevation as the inlet
Separate instructions are provided with the flue detailing the installation of the flue parts.
Flue pipes must include a condensate drain if the total flue height exceeds 1.5m. There
is a special condensate drain collector piece available through Rinnai or your supplier.
For flue runs requiring a drain the horizontal sections on the appliance side of any verti-
cal runs should slope towards the appliance, and the flue should be bracketed to prevent
sagging. If the terminal is horizontal it should slope gently to the outside to prevent in-
gress of rain.
The drain pipe should be run in 22mm PVC, uPVC, or ABS pipe, copper is not recom-
mended. The drain pipe MUST be trapped. A trap with pipe is available from Rinnai or
your supplier.
Although the flue and appliance have been specially designed to prevent condensation
in the flue for short runs (under 1.5m) care should be given to the placement of the
terminal to prevent risk in the unlikely event of condensation. Condensation water can
cause burns, and during winter could cause a slip hazard. It is the responsibility of the
installer to decide the best place.
31