August 2023
6
Configuration parameters
Emerson recommends that you verify various configuration
parameters prior to installing the transmitter into the process:
•
Alarm and saturation levels
•
Damping
•
Process variables
•
Range values
•
Tag
•
Transfer function
•
Units
Complete the following procedural steps to verify these parameters.
See
Figure 6-1
NOTICE
Emerson recommends installing the latest DD to ensure full
functionality. Download the latest DD at
Drivers | Emerson
Procedure
1. Set alarm and saturation values: Device Settings → Setup
Overview → Alarm and Saturation Values.
2. Set damping: Device Settings → Setup Overview → Output.
3. Set process variables:
•
•
4. Set range values: Device Settings → Setup Overview → Output.
5. Set tag: Device Settings → Setup Overview → Device.
6. Set transfer function: Device Settings → Setup Overview →
Output.
7. Set units:
•
Quick Start Guide
for a full menu tree.
US.
Primary variable: Device Settings → Setup Overview →
Output
Secondary/Tertiary/Quaternary variables: Device Settings
→ Communication → HART → Variable Mapping
Pressure units: Device Settings → Setup Overview →
Output
Quick Start Guide
Software Downloads &
19