n 6 feet of appliances
NFPA 72 states: "Smoke alarms in rooms with ceiling slopes greater than 1 ft in 8 ft (.3m in 2.4 m) horizontally
shall be located on the high side of the room." NFPA 72 states: "A row of detectors shall be spaced and located
within 3 ft (0.9m) of the peak of the ceiling measured horizontally."
feet of appliances
Not within 6 feet of appliances
10
ANYWHERE ALONG
THIS BOLD SURFACE
Locations permitted for smoke
alarms and smoke detectors
on tray-shaped ceilings.
Figure 6-B
Figure 6-C