Toshiba MMD-AP0721HP-UL1 Service Manual page 64

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
control
Sub-code
code
F29
F31
F31
01: Compressor 1 side
02: Compressor 2 side
H01
H01
01: Compressor 1 side
02: Compressor 2 side
H02
H02
01: Compressor 1 side
02: Compressor 2 side
H03
H03
H05
H05
H06
H06
*1 Total shutdown in case of header unit
Continued operation in case of follower unit
Location
System
of
Description
status
detection
Indoor
Other indoor
Stop of
trouble
unit
corresponding
unit
I/F
Outdoor
All stop *1
EEPROM
trouble
IPDU
Compressor
All stop
breakdown
IPDU
Compressor
All stop
trouble (lockup)
MG-CTT
trouble
IPDU
Current
All stop
detection
circuit trouble
I/F
TD1 sensor
All stop
miswiring
(incomplete
insertion)
I/F
Activation of
All stop
low-pressure
protection
- 64 -
Trouble detection
Check items (locations)
condition(s)
Indoor P.C. board does not
• Check for defect in indoor P.C.
operate normally.
board (faulty EEPROM)
Outdoor P.C. board (I/F)
• Check power supply voltage.
does not operate normally.
• Check power supply noise.
• Check for defect in outdoor
P.C. board (I/F).
Inverter current detection
• Check power supply voltage.
circuit detects overcurrent
(AC460V ± 10%).
and shuts system down.
• Check for defect in
compressor.
• Check for possible cause of
abnormal overloading.
• Check for defect in outdoor
P.C. board (A3-IPDU).
• Check for defect in
Overcurrent is detected
several seconds after
compressor.
startup of inverter
• Check power supply voltage.
compressor.
(AC460V ± 10%).
• Check compressor system
wiring, particularly for open
phase.
• Check connection of
connectors/terminals on A3-
IPDU P.C. board.
• Check conductivity of case
heater.
(Check for refrigerant
problem inside
compressor.)
• Check for defect in outdoor
P.C. board (A3-IPDU).
• Check outdoor MG-CTT.
Current flow of at least
• Check current detection circuit
specified magnitude is
wiring.
detected despite inverter
• Check defect in outdoor P.C.
compressor having been
board (A3-IPDU).
shut turned off.
Discharge temperature of
• Check installation of TD1
compressor 1 (TD1) does
sensor.
not increase despite
• Check connection of TD1
compressor being in
sensor connector and wiring.
operation.
• Check resistance
characteristics of TD1 sensor.
• Check for defect in outdoor
P.C. board (I/F).
Low-pressure Ps sensor
• Check service valves to
detects operating
confirm full opening
pressure lower than
(both gas and liquid sides).
2.9psi(0.02MPa)
• Check outdoor PMVs for
clogging (PMV1, 3).
• Check for defect in SV2 or SV4
circuits.
• Check for defect in low-
pressure Ps sensor.
• Check indoor filter for clogging.
• Check valve opening status of
indoor PMV.
• Check refrigerant piping for
clogging.
• Check operation of outdoor fan
(during heating).
• Check for insufficiency in
refrigerant quantity.