Toshiba MMD-AP0721HP-UL1 Service Manual page 17

Table of Contents

Advertisement

NO.
Item
1. In heating operation, the upper limit of the fan tap is set according to the
Cold air
discharge
lower of whichever is the higher between TC2 sensor and TCJ sensor
prevention
temperatures, on the one hand, and TC1 sensor temperature, on the
control
other.
• If the fan continuously operates in zone B for 6 minutes, it automatically
• During defrosting, the control point is shifted by +10.8°F[6°C].
6
Freeze
1. During cooling, the air conditioner is operated in the manner described
prevention
below according to the temperature readings of the TC1, TC2 and TCJ
control (low
sensors.
temp. release)
• If zone J operation is detected for 5 minutes, the air conditioner is forced
• In zone K, the timer is put on pause, with the current timer count
• If zone I operation is detected, the timer count is cleared, and the air
• If continuous zone J operation forces the air conditioner into thermostat
Termination conditions
1) TC1 ≥ 54°F (12°C), TC2 ≥ 54°F (12°C), and TCJ ≥ 54°F (12°C)
7
2) Passage of 20 minutes after stoppage
2. During cooling, the air conditioner is operated in the manner described
below according to the temperature readings of the TC2 and TCJ sensors.
• If zone M operation is detected for 45 minutes, the air conditioner is
• In zone N, the timer is put on pause, with the current timer count
• When the air conditioner goes back into zone M, timer count is resumed
• If zone L operation is detected, the timer count is cleared, and the air
Reset conditions
1) TC1 ≥ 54°F(12°C), TC2 ≥ 54°F(12°C) and TCJ ≥ 54°F(12°C)
2) After 20 minutes elapsed from the stop.
Specification outline
moves into zone C.
°F(°C)
90 (32)
D
86 (30)
C
E
82 (28)
75 (26)
68 (20)
61 (16)
into thermostat OFF.
retained.
conditioner returns to normal operation.
OFF, the indoor fan is operated in breeze mode until it moves into zone I.
The control is terminated under the following conditions:
°F(°C)
P1
a
I
K
Q1
J
forced into thermo OFF.
retained.
from the retained value.
°F(°C)
L
P2
N
Q2
M
conditioner returns to normal operation.
A zone: OFF
B zone: 79°F(26˚C) or above and
below 82°F(28˚C)
breeze
C zone: 82°F(28˚C) or above and
below 86°F(30˚C)
Low
D zone: 86°F(30˚C) or above and
below 90°F(32˚C)
Medium
B
E zone: High
A
TC1
TC2, TCJ
14˚F
50˚F (10˚C)
P1
(–10˚C)
32˚F(0˚C)
7˚F(14˚C)
Q1
TC2, TCJ
41°F(5°C)
P2
28°F(2°C)
Q2
- 17 -
Remarks
TCJ: Indoor heat
exchanger
sensor
temperature
In zones D and E,
priority is given
to the remote
control fan
speed setting.
In zone A,
"HEATING
STANDBY
"
is displayed.
TC1:
Indoor heat
exchanger
sensor
temperature
* With models
without TC2,
TC2 is not
part of the
control
parameters.