NME1254R & FME1504R
FOR THE PLUMBER
Water Inlet
The recommended water supply is cold water.
Use 3/8" O.D. copper tubing, connect to the 3/8"
male flare at the back of the cabinet. Install a hand
valve near the machine to control the water supply.
WATER
INLET
3/8" FLARE
HAND SHUT
OFF VALVE
CONNECT TO
COLD WATER
FIELD INSTALLED
FILTER
(OPTIONAL)
CONFORM TO ALL APPLICABLE CODES
There is one 3/4" FPT drain at the back of the
cabinet, the drain line is of the gravity type, and 1/4
inch per foot fall is an acceptable pitch for the drain
tubing. There should be a vent at the highest point
of the drain line, and the ideal drain receptacle
would be a trapped and vented floor drain. Use
only 3/4" rigid tubing.
Storage Bin: Install a separate drain line. Insulation
of this drain line is recommended.
January 2000
Page 8
Drains
ICEMAKER DRAIN
3/4" FPT
BIN DRAIN
3/4" FPT