2.14 Differential Protection and Its Protected Objects
2.14.4

Current Transformer Requirements

The differential protection is of decisive importance for the requirements that the current transformers must
meet. The high-speed trip stage (IDiff >>) uses instantaneous values and can therefore reliably trip high-current
internal short-circuits. For determination of the primary CT rated current, in practice the general usual proce-
dures are used. It must be selected equal to or greater than the rated current of the protected object.
2.14.4.1 Functional Description
Design recommendations
The external short circuit determines the requirements that the current transformers must meet because of the
possible DC current component. In case of a short-circuit flowing through the power transformers, a minimum
of 5 ms should elapse before current transformer saturation occurs. The two following tables show the design
specifications. The IEC 60044-1 and IEC 60044-6 standards were used in these tables. The equations for cal-
culating the requirements as knee-point voltages are listed in table 2-7.
Table 2-5
Required operational overcurrent factor
with
K
td
I
pSSC
I
pN
R
BC
R
BN
R
Ct
126
Overcurrent Factors
Transient dimensioning factor
Primary symmetric short circuit current
Primary CT rated current
Connected load
Rated load
Internal load
Resulting rated overcurrent factor