Download Print this page

Delta PMU-27V155WC A Series Instruction Manual

Advertisement

Quick Links

Instruction Manual
1.
Safety Instructions
Must select correct AC input voltage range through selectable switch before turning on (Refer to
Fig. 1, ⑥).
To ensure sufficient convection cooling, always maintain a safety distance of ≥ 20mm from all
ventilated surfaces while the device is in operation.
The device is not recommended to be placed on low thermal conductive surface, for example,
plastics.
Note that the enclosure of the device can become very hot depending on the ambient temperature
and load of the power supply. Do not touch the device while it is in operation or immediately after
power is turned OFF. Risk of burning!
Do not touch the terminals while power is being supplied. Risk of electric shock.
Prevent any foreign metal, particles or conductors to enter the device through the openings during
installation. It can cause: Electric shock; Safety Hazard; Fire; Product failure
Battery need to be protected from short circuit while installation & servicing. Danger of explosion.
Signal cable should not interact with AC Input.
Warning: When connecting the device, secure Earth connection before connecting L and N. When
disconnecting the device, remove L and N connections before removing the Earth connection.
2.
Device Descriptions
Refer to Fig. 1.:
䐟 Input & Output terminal block connector
䐠 DC voltage adjustment potentiometer (24V - 28V)
䐡 Green LED ON = DC OK (Normal operation through mains supply or through battery when
operating in buffering mode)
մ Red LED ON
= Battery reverse polarity
յ Battery charging current adjustment potentiometer (Factory Setting: 1A)
Max charging current shall not exceed 1.5A (Refer to Fig. 1, ⑤).
ն AC selectable switch
䷻ Signal connector - JST: XHP-4 (for PMU-27V155WCCA only)
3.
Installation of the Device
Refer to Fig. 2.:
䑵 Mounting holes for the power supply assembly onto the mounting surface. The power supply shall
be mounted on minimum 2 mounting holes using M3 screw minimum 5mm length.
䑶 This surface belongs to customer's end system or panel where the device is mounted.
䑷 Connector
Use flexible cable (stranded or solid), AWG No. 16-14.
The torque at the Connector shall not exceed 13 Kgf.cm. The insulation stripping length should not
exceed 0.275" or 7mm (Refer to Fig. 3).
4.
Battery Information
Battery Capacity
Battery Cut-off Voltage
Battery Low (Deep Discharge) Detection*
*If the battery is deep discharged, the power supply will not recognize the battery.
5.
Installation of Mounting Accessories
Refer to Fig. 4.:
Only use M3 screw ≤ 2.5mm through the base mounting holes. This is to keep a safety distance
between the screw and internal components.
Recommended mounting tightening torque: 4~8 Kgf.cm.
REV.00
3.2AH - 15AH
20V ± 1V
17V ± 1V
PMU-27V155WCBA (no signal connector)
Ventilated surface
Side surface
Top surface
5
6
Base surface
1
2
400mm.(Ref.)
Signal connector
7
JST: XHP-4
Fig. 1. Device Descriptions
Side Mounting (Vertical)
Base Mounting (Vertical)
A
A
A
A
A
A
C
C
C
C
C
C
B
B
B
Fig. 2. Mounting Orientation
7 mm
Lug
Stripped wire
Fig. 3. Wire Type
PMU-27V155WC□A
PMU-27V155WCCA (with signal connector)
Ventilated surface
6
Base surface
4
3
1
Pin No.
Description
1
DC OK
2
Low Battery
3
GND
4
AC OK
Side Mounting (Horizontal)
A
A
B
B
A
B
B
B
B
Mounting
Chassis of
accessories
the device
Mounting
screw
2.5mm
max.
Fig. 4. Mounting Screw
www.DeltaPSU.com
Side surface
Top surface
5
3
4
2
7
C
C
C

Advertisement

loading

Summary of Contents for Delta PMU-27V155WC A Series

  • Page 1 Instruction Manual PMU-27V155WC□A Safety Instructions PMU-27V155WCBA (no signal connector) PMU-27V155WCCA (with signal connector) • Must select correct AC input voltage range through selectable switch before turning on (Refer to Fig. 1, ⑥). Ventilated surface Ventilated surface • To ensure sufficient convection cooling, always maintain a safety distance of ≥ 20mm from all Side surface Side surface ventilated surfaces while the device is in operation.
  • Page 2 PMU-27V155WC□A 使用說明書 使用说明书 1. 安全規範 1. 安全规范 • 通电前需选择正确的交流输入电压 (依据图一⑥的位置)。 • 通电前需选择正确的交流输入电压 (依据图一⑥的位置)。 • 與通風表面保持至少 20mm 的安全距離,以確保對流冷卻充分。 • 与通风表面保持至少 20mm 的安全距离,以确保对流冷却充分。 • 本產品不適合擺放在低熱導體,例如: 塑膠。 • 本产品不适合摆放在低热导体,例如: 塑胶。 • 受環境溫度及產品負載的影響,本機外殼溫度會很高,因此在上電時或切斷電源後短時間內 • 受环境温度及产品负载的影响,本机外壳温度会很高,因此在上电时或切断电源后短时间内 不要觸摸本機,以免燙傷。 不要触摸本机,以免烫伤。 • 請勿在上電時觸摸連接端子,以防電擊危險。 • 请勿在上电时触摸连接端子,以防电击危险。 • 安裝過程中,應避免金屬元件或金屬導體通過空隙或通風孔進入到產品內,否則會引起下列 • 安装过程中,应避免金属元件或金属导体通过空隙或通风孔进入到产品内,否则会引起下列 狀況。-電擊;安全危害;火災;產品異常 状况。-电击;安全危害;火灾;产品异常 • 當安裝和維修時,需要保護電池以避免短路進而防止發生爆炸的危險。 • 当安装和维修时,需要保护电池以避免短路进而防止发生爆炸的危险。 • 信號線不能與交流輸入線纏繞在一起,以免交互影響。 • 信号线不能与交流输入线缠绕在一起,以免交互影响。...
  • Page 3 Instruction Manual PMU-27V155WL□A Safety Instructions • Must select correct AC input voltage range through selectable switch before turning on (Refer to Side surface Fig. 1, ⑥). TOP SIDE • To ensure sufficient convection cooling, always maintain a safety distance of ≥ 20mm from all ventilated surfaces while the device is in operation. • For safety reasons, please ensure the mounted device is kept at ≥ 7mm safety distance at the top and left side from other components and equipments (Refer to Fig. 2). • The device is not recommended to be placed on low thermal conductive surface, for example, plastics.
  • Page 4 PMU-27V155WL□A 使用說明書 使用说明书 1. 安全規範 1. 安全规范 • 通电前需选择正确的交流输入电压 (依据图一⑥的位置)。 • 通电前需选择正确的交流输入电压 (依据图一⑥的位置)。 • 與通風表面保持至少 20mm 的安全距離,以確保對流冷卻充分。 • 与通风表面保持至少 20mm 的安全距离,以确保对流冷却充分。 • 基於安全考量,上方與靠近左側的元器件和設備必須與本產品保持至少 7mm 的安全距離 • 基于安全考量,上方与靠近左侧的元器件和设备必须与本产品保持至少 7mm 的安全距离 (請參考圖二)。 (请参考图二)。 • 本產品不適合擺放在低熱導體,例如: 塑膠。 • 本产品不适合摆放在低热导体,例如: 塑胶。 • 受環境溫度及產品負載的影響,本機外殼溫度會很高,因此在上電時或切斷電源後短時間內 • 受环境温度及产品负载的影响,本机外壳温度会很高,因此在上电时或切断电源后短时间内 不要觸摸本機,以免燙傷。 不要触摸本机,以免烫伤。 • 請勿在上電時觸摸連接端子,以防電擊危險。 • 请勿在上电时触摸连接端子,以防电击危险。 • 安裝過程中,應避免金屬元件或金屬導體通過空隙或通風孔進入到產品內,否則會引起下列 • 安装过程中,应避免金属元件或金属导体通过空隙或通风孔进入到产品内,否则会引起下列 狀況。-電擊;安全危害;火災;產品異常 状况。-电击;安全危害;火灾;产品异常...

This manual is also suitable for:

Pmu-27v155wcbaPmu-27v155wcca