Installation guide
Pressure switch
KP 15, KP 15A, KP 17W, KP 17B, KP 17WB
Refrigerants:
R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D,
R448A, R449A, R450A, R452A, R507A, R513A, R717*)
For complete list of approved refrigerants, go to
http://products.danfoss.com/all-products/
*) only for KP 15A
Ambient temperatures / Mounting requirements
t
min. KP 15: -40 °C (-40 °F)
1
t
min. KP 17: - 25 °C (-13 °F)
1
t
max.: 65 °C (149 °F)
1
Relative humidity RH: 30 – 98%
Vibrations resistance: 4 g (10 – 1000 Hz)
Connections
12 (15/32 in)
KP 15A
17 mm
(11/16 in)
14 mm
(9/16 in)
© Danfoss | Climate Solutions | 2021.05
Mounting
15% Ag
KP 15, KP 17
14 mm
(9/16 in)
KP 15, KP 17
KP 15, KP 17
Test pressure (P
)
test
Type
Regulation range Max. working pressure PS/MWP
LP: -0.2 – 7.5 bar
KP 15
HP: 8 – 32 bar
KP 15
LP: -0.9 – 7 bar
LP man.
HP: 8 – 32 bar
reset
LP: -0.2 – 7.5 bar
KP 17
HP: 8 – 32 bar
Enclosure
Max. 100 °C
(212 °F)
A: 8 – 32 UNC (M4)
C: Enclosure IP44
(EN 60529)
KP 15A
p
max.
test
35 bar (510 psig)
PS/MWP
p
max.
test
20 bar (285 psig)
PS/MWP
17 bar/245 psig
35 bar/510 psig
17 bar/245 psig
35 bar/510 psig
17 bar/245 psig
35 bar/510 psig
B: Enclosure IP30
(EN 60529)
max. 3 mm
(1/8 in)
AN211686434433en-000701 | 1

Advertisement

loading

Summary of Contents for Danfoss KP 15

  • Page 1 Installation guide Pressure switch KP 15, KP 15A, KP 17W, KP 17B, KP 17WB KP 15, KP 17 KP 15, KP 17 KP 15A Refrigerants: R22, R134a, R404A, R407A, R407C, R407F, R422B, R422D, R448A, R449A, R450A, R452A, R507A, R513A, R717*) For complete list of approved refrigerants, go to http://products.danfoss.com/all-products/...
  • Page 2 LP, aut. reset LP, man. reset Manual trip function Convertible reset KP 15: LP/HP convertible, KP 17WB: HP convertible Insert a screwdriver into the slot on the lock disc and TRIP: turn it to desired reset configuration. use FINGERS ONLY!
  • Page 3 KP pressure switches. Danfoss shall not be responsible for any kind of direct and indirect or consequential damage or loss, including, but not limited to, loss of property, production, loss of profit, human injury arising out of the explosion or fire caused by the flammable nature of refrigerant.

This manual is also suitable for:

Kp 15aKp 17wKp 17bKp 17wb