Danfoss KP 15 Instructions

Danfoss KP 15 Instructions

Pressure controls

Advertisement

Quick Links

Instructions
Types
The controls can be used with CFC, HFC, HCFC refrigerants.
CAUTION: Do not install these controls on
ammonia systems
KP 15 man. (LP) / man. (HP) reset
Ambient temperatures
t
min. KP 15, KP 25:
1
KP 17W, KP 17B:
t
max.
1
CAUTION: Do not mount the control in a position where dirt, sediment,
or oil will aff ect the operation of the control.
Enclosure
CAUTION: The mounting panel must be plane to avoid damage of control.
©Danfoss A/S
Pressure Controls
KP 15, KP 17W, KP 17B, KP 25
KP 15, KP 17B auto. (LP) / man. (HP) reset
–40°F (–40°C)
–13°F (–25°C)
150°F (65°C)
KP 15, KP 17W, KP 25 auto. (LP) / auto (HP) reset
Test pressure (p
)
TEST
p
max.
test
505 psig
(35 bar p
)
e
p
max.
test
285 psig
(20 bar p
)
e
RI5AK222 - 520H0146

Advertisement

loading

Summary of Contents for Danfoss KP 15

  • Page 1 CAUTION: Do not install these controls on ammonia systems KP 15 man. (LP) / man. (HP) reset KP 15, KP 17B auto. (LP) / man. (HP) reset KP 15, KP 17W, KP 25 auto. (LP) / auto (HP) reset Ambient temperatures Test pressure (p TEST max.
  • Page 2 Controls with low pressure (LP) and high pressure (HP) signal) 240 V d.c. 12 W pilot duty KP 15 and KP 17W. Only code nos.: 060-2024 060-2027 060-2030 See label inside cover 060-2026 060-2029 060-2031 (stamped on top of control)
  • Page 3 LP man. reset is possible only after system pressure has risen above cut-in value. HP man. reset is possible only after system pressure has dropped below cut-out value. Convertible reset KP 15, code nos.: 060-2025, 060-2028 Reset options Turn plate to desired LP man. LP-auto.
  • Page 4 Setting Low pressure (LP) side setting High pressure (HP) side setting KP 15, KP 17W, KP 17B and KP 25 KP 15 with LP man. reset only KP 15, KP 17W, KP 17B and KP 25 with LP auto. reset only KP 15 with convertible LP auto.)

This manual is also suitable for:

Kp 17wKp 25Kp 17b