Installation - Siemens SITRANS P LH300 Compact Operating Instructions

Pressure transmitter
Table of Contents

Advertisement

4.2

Installation

Figure 4-1
1. Install the pressure transmitter suspended downward on the cable.
2. To prevent measuring errors, fasten the pressure transmitter for moved process media.
3. Fasten the pressure transmitter by means of a guide tube or an additional weight on the
transmitter (max. tensile force on connecting cable 360 N).
4. Fasten the cable above the container with the anchor clamp.
5. Connect the cable itself with the cable box.
6. Mount the cable box at a location appropriate to its degree of protection (IP66) in the vicinity
of the measuring point.
7. To ensure proper functioning, make sure that the entry openings on the protective cover of
the pressure transmitter do not get soiled and that the process medium does not freeze on
the pressure transmitter.
SITRANS LH300 Transmitter for Hydrostatic Level
Compact Operating Instructions, 11/2022, A5E37897183-AD
Level
Measurement reference height
Mounting the pressure transmitter (example with protective cover made of PPE)
Installing/mounting
4.2 Installation
17