Specifications Of Standard Wiring Components; To Connect The Electrical Wiring To The Outdoor Unit - Daikin VRV 5-S RXYSA4A7V1B Installation And Operation Manual

Table of Contents

Advertisement

Model
RXYSA4_V
RXYSA5_V
RXYSA6_V
16.2
Specifications of standard wiring
components
NOTICE
We recommend using solid (single-core) wires. If stranded
wires are used, slightly twist the strands to consolidate the
end of the conductor for either direct use in the terminal
clamp or insertion in a round crimp-style terminal. Details
are described in "Guidelines when connecting the electrical
wiring" in the installer reference guide.
Component
(a)
Power supply
MCA
cable
Voltage
Phase
Frequency
Wire size
Interconnection
Voltage
cable (indoor ↔
Wire size
outdoor)
Recommended field fuse
Earth leakage circuit
30 mA – MUST comply with national
breaker / residual current
device
(a)
MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of combination with indoor units for
exact values).
16.3
To connect the electrical wiring to
the outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover. See
unit" [ 4  23].
2 Connect the interconnection cable as follows:
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600329-1E – 2023.02
Minimum S
value
sc
122.95 kVA
154.07 kVA
173.05 kVA
RXYSA*_V
RXYSA*_Y
27.0 A
13.6 A
220-240 V
380-415 V
1~
3N~
50 Hz
MUST comply with national wiring
regulation.
3-core cable
5-core cable
Wire size based on the current, but
not less than:
2
2
4.0 mm
2.5 mm
220-240 V
Only use harmonised wire providing
double insulation and suitable for
applicable voltage.
2-core cable
0.75-1.5 mm²
32 A, C curve
16 A, C curve
wiring regulation
"13.2.1  To open the outdoor
16 Electrical installation
V
X4M
TO IN/D
a
a
b
F1 F2
a
a
b
F1 F2
a
a
Interconnection cable (see
components" [ 4  31] for wiring
standard wiring
requirements)
b
Terminal board (field supply)
c
Shielded cable
NOTICE
▪ Use shielded wire for the interconnection cable.
▪ Y1 only: connect the earth (a) to the support frame of
the terminal X2M.
a
3 Connect the power supply as follows:
V
1~ 50 Hz
220-240 V
L
a
b
c
X1M
L
N
a
Earth leakage circuit breaker
b
Fuse
c
Power supply cable (see
components" [ 4  31] for wiring requirements)
wiring
4 Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate and route the wiring
according to the illustration below.
Y
X2M
TO IN/D
TO OUT/D
a
a
F1 F2
F1 F2
a
a
F1 F2
F1 F2
"16.2 Specifications of
Y
3N~ 50 Hz
380-415 V
L1 L2 L3
X1M
L1 L2 L3
N
"16.2 Specifications of standard
Installation and operation manual
31