Daikin RX50KV1B Installation Manual page 12

Hide thumbs Also See for RX50KV1B:
Table of Contents

Advertisement

Wiring
WARNING
• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical
shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• Be sure to install an earth leak detector. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to
prevent malfunctioning of the earth leak detector itself.)
• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
• Equipment complying with EN/IEC 61000-3-12
• Do not turn ON the safety breaker until all work is completed.
1) Strip the insulation from the wire (20mm).
2) Connect the inter-unit wire between the indoor
and outdoor units so that the terminal
numbers match. Tighten the terminal screws
securely. We recommend a flathead
screwdriver be used to tighten the screws.
Appearance of outdoor units may differ from some models.
2
1
3
L
1
L
2
Observe the notes mentioned below when wiring to the power supply terminal block.
Precautions to be taken for power supply wiring.
(1)
European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and ≤75 A per phase.
9
(1)
Power supply
terminal block
Shape wires so
that the protection
plate and conduit
mounting plate fit
securely.
Firmly fix the wires with
the terminal screws.
Inter-unit wire
4-core 1.5mm² or more
H05RN
Indoor
unit
Firmly fix the wires with
the terminal screws.
Outdoor unit
Power supply wire
3-core 2.5mm² or more
H05RN
Safety
Earth leakage
breaker
circuit breaker
20A
Earth
Service lid
1
2
3
Screws
Power
supply
50Hz 220-240V
English

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rx60kv1bRx71kv1b

Table of Contents