Example: Total refrigerant charge in the system is 45 kg and room
3
volume is 300  m
. 45/300=0.15, which is >QLMV (0.074) and
<QLAV (0.18), therefore install at least 1 appropriate measure in the
room.
QLAV
70
65
a
60
55
50
45
40
35
30
25
20
15
10
5
0
0
50
100 150
200 250 300 350
400
450
  12‒2 Example graph for calculation
A
Refrigerant charge
B
Room volume
a
2 appropriate measures required
b
1 appropriate measure required
c
No measure required
For occupancies on the lowest underground floor of the
building
If the total refrigerant charge
(kg) divided by the room
(a)
3
volume
(m
) is...
<RCL
>RCL and ≤QLMV
>QLMV and <QLAV
>QLAV
(a)
For occupied spaces with a floor area exceeding 250 m
2
250 m
as the floor area for determination of the room volume
(Example: even if the room area is 300 m
is 2.5 m, calculate the room volume as 250 m
Example: Total refrigerant change in the system is 45 kg and room
3
volume is 300 m
. 45/300=0.15, which is >RCL (0.072) and <QLAV
(0.18), therefore install at least 2 appropriate measures in the room.
QLAV
70
65
a
60
55
50
45
40
35
30
25
20
15
10
5
0
0
50
100 150
200 250 300 350
400
450
  12‒3 Example graph for calculation
A
Refrigerant charge limit
B
Room volume
a
Installation is not allowed
b
2 appropriate measures required
c
1 appropriate measure required
d
No measure required
FXFN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
3P672850-1B – 2022.01
QLMV
b
c
500
550
600 650 700 750 800 850 900 950 1000
B (m³)
...the number of appropriate
measures must be at least...
0
1
2
Value CANNOT be exceeded!
2
, use
2
and the room height
2
3
×2.5 m=625 m
)
QLMV
RCL
b
c
d
500
550
600 650 700 750 800 850 900 950 1000
B (m³)
INFORMATION
Even if there is no refrigerating system on the lowest floor,
where the largest system charge (kg) in the building
divided by total volume of the lowest floor (m
value for QLMV, provide a mechanical ventilation in
accordance with EN 378-3:2016.
12.2

Mounting the indoor unit

12.2.1

Guidelines when installing the indoor unit

INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
▪ Decoration panel. Install the decoration panel always after
installing the unit.
NOTICE
After installing the decoration panel:
▪ Make sure there is no gap between the unit body and
the decoration panel. Possible consequence: Air
might leak and cause dew drop.
▪ Make sure no oil remains on the plastic parts of the
decoration
panel.
Degradation and damage of plastic parts.
▪ Ceiling strength. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.
▪ For existing ceilings, use anchors.
▪ For new ceilings, use sunken inserts, sunken anchors or other
field supplied parts.
A
50~100 mm: In case of installation with standard panel
100~150 mm: In case of installation with fresh air intake
kit or design panel
130~180 mm: In case of installation with auto cleaning
decoration panel
a
Ceiling slab
b
Anchor
c
Long nut or turnbuckle
d
Suspension bolt
e
Suspended ceiling
▪ Suspension bolts. Use M8~M10 suspension bolts for installation.
Attach the hanger bracket to the suspension bolt. Fix it securely
using a nut and washer from the upper and lower sides of the
hanger bracket.
710
(mm)
a1
Nut (field supply)
a2
Double nut (field supply)
b
Washer (accessories)
c
Hanger bracket (attached to the unit)
12 Unit installation
3
) exceed the
Possible
consequence:
a
b
c
d
e
a1
b
c
b
a2
Installation and operation manual