8 Troubleshooting

INFORMATION
During detection of the refrigerant leakage, the contact
between terminals T1 and T2 disconnects. During normal
operation, the contact between terminals T1 and T2 is
closed (acting as a short circuit).
1 If field supplied stop-valves are NOT installed: Close the stop
valves of the gas and liquid pipe on the outdoor unit.
2 If field supplied shut-off valves are installed: If the refrigerant
leak to the room has stopped, you can use the air conditioner
for other rooms where the refrigerant leak did NOT occur.
3 Locate and repair the cause of the refrigerant leak. If
necessary, replace the indoor unit.
4 Refill the refrigerant if needed.
5 Perform manual power reset and resume operation.
NOTICE
After the refrigerant leakage is detected, the unit will send
a signal at regular intervals to confirm if the CO
concentration is at a safe level. Even when the CO
concentration is at a safe level, do NOT resume operation
before the fault is fixed and the refrigerant is refilled.
8
Troubleshooting
If one of the following malfunctions occur, take the measures shown
below and contact your dealer.
WARNING
Stop operation and shut OFF the power if anything
unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may
cause breakage, electrical shock or fire. Contact your
dealer.
The system MUST be repaired by a qualified service person.
Malfunction
If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does NOT function properly.
If water leaks from the unit.
Installation and operation manual
12
2
2
Measure
Turn OFF all main power
supply switches to the
unit.
Stop operation.
Malfunction
The operation switch does NOT function
properly.
If the user interface displays
error code.
The user interface displays error code
A0 or U9 (or
), the fan stops and you
can hear a warning sound from the user
interface (in case of Madoka) or from
another safety alarm in combination
with a gas detection device (if installed).
If the system does NOT operate properly except for the above
mentioned cases and none of the above mentioned malfunctions is
evident, investigate the system in accordance with the following
procedures.
INFORMATION
Refer
to
the
reference
www.daikineurope.com/support-and-manuals/product-
information/
for more troubleshooting tips.
If after checking all above items, it is impossible to fix the problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).
9

Relocation

Contact your dealer for removing and reinstalling the total unit.
Moving units requires technical expertise.
10

Disposal

NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
Measure
Turn OFF the power
supply.
Notify your installer and
or an
report the error code. To
display error codes, see
the reference guide of the
user interface.
A refrigerant leak may be
detected (see
"7.3.1 About
refrigerant leak
detection" [ 4  11]).
guide
located
on
http://
FXFN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
3P672850-1B – 2022.01