Connectable components
12.2 PP 72/48D PN and PP 72/48D 2/2A PN
Analog inputs
The module has two analog inputs. These can optionally be assigned parameters as voltage,
current or PT100 input.
• "Voltage input" operating mode:
• "Current input" operating mode:
• "PT100" operating mode
Note
The analog inputs are only enabled following the parameter assignment.
Cycle time of the analog value accumulation: 20 ms per channel
NOTICE
Protection from overvoltage
If the PT100 operating mode is selected, the hardware is protected against overvoltage.
In the event of an error the following occurs:
1. An error bit is set which is then communicated to the PLC.
2. The module is shut down.
134
Parameter
Input range (rated value)
Permissible range overstepping
Resolution
Accuracy
Internal resistance Ri
Parameter
Input range (rated value)
Permissible range overstepping
Resolution
Accuracy
Internal resistance Ri
Parameter
Input range (rated value)
Standard
Resolution
Accuracy
Internal resistance Ri
Value
- 10 V to + 10 V
- 11.75 V to + 11.75 V
16-bit (incl. sign)
+/-0.5%
100 KOhm
Value
- 20 mA to + 20 mA
- 23.5 mA to + 23.5 mA
16-bit (incl. sign)
+/-0.5%
133 ohm
Value
-200 °C to +259 °C
EN60751
16-bit (incl. sign)
+/- 2 °C
>> 10 kOhm
Equipment Manual, 09/2022, A5E51087503B AC