Location; Rigging And Handling; Zj037-061 Unit Limitations - York ZJ037-061 Instruction Manual

Table of Contents

Advertisement

Table 1: ZJ037-061 Unit Limitations
Size
(Tons)
037
(3.0)
049
(4.0)
061
(5.0)

Location

Use the following guidelines to select a suitable location for
these units:
1.
Unit is designed for outdoor installation only.
2.
Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on
either north or east side of building.
3.
Suitable for mounting on roof curb.
4.
For ground level installation, use a level concrete slab with
a minimum thickness of 4 inches. The length and width
should be at least 6 inches greater than the unit base rails.
Do not tie slab to the building foundation.
5.
Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed on a
solid, level roof curb or appropriate angle iron frame.
6.
Maintain level tolerance to 1/2" across the entire width and
length of unit.
Excessive exposure of this furnace to contaminated
combustion air may result in equipment damage or
personal injury. Typical contaminates include:
permanent wave solution, chlorinated waxes and
cleaners, chlorine based swimming pool chemicals,
water softening chemicals, carbon tetrachloride,
Halogen type refrigerants, cleaning solvents (e.g.
perchloroethylene), printing inks, paint removers,
varnishes, hydrochloric acid, cements and glues, anti-
static fabric softeners for clothes dryers, masonry acid
washing materials.
Clearances
All units require particular clearances for proper operation and
service. Installer must make provisions for adequate
combustion and ventilation air in accordance with section 5.3 of
Air for Combustion and Ventilation of the National Fuel Gas
Johnson Controls Ducted Systems
Model
Unit Voltage
208/230-3-60
ZJ
460-3-60
575-3-60
208/230-3-60
ZJ
460-3-60
575-3-60
208/230-3-60
ZJ
460-3-60
575-3-60
Unit Limitations
Applied Voltage
Min
187
432
540
187
432
540
187
432
540
Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections 7.2,
7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in Canada) -
Latest Edition, and/or applicable provisions of the local building
codes. Refer to Table 5 for clearances required for combustible
construction, servicing, and proper unit operation.
Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combustion air
inlet or vent outlets.

Rigging And Handling

Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig the
unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreader bars, whose length
exceeds the largest dimension across the unit, MUST be used
across the top of the unit.
If a unit is to be installed on a roof curb other than a
®
York
roof curb, gasketing must be applied to all
surfaces that come in contact with the unit underside.
Before lifting, make sure the unit weight is distributed
equally on the rigging cables so it will lift evenly.
Units may be moved or lifted with a forklift. Slotted openings in
the base rails are provided for this purpose.
LENGTH OF FORKS MUST BE A MINIMUM OF 60 INCHES.
5565591-YIM-B-1019
Outdoor DB Temp
Max
Max (°F)
252
125
504
125
630
125
252
125
504
125
630
125
252
125
504
125
630
125
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zj seriesZj037-049Zj061Zj037

Table of Contents