Flowmeter Status - Siemens SITRANS F Modbus RTU RS 485 Operating Instructions Manual

Communication modules
Hide thumbs Also See for SITRANS F Modbus RTU RS 485:
Table of Contents

Advertisement

A.12

Flowmeter status

Table A-24
Flowmeter status
MODBUS regis‐
MODBUS ad‐
ter
dress
4:03201
3200
4:03202
3201
4:03203
3202
4:03204
3203
4:03205
3204
4:03206
3205
4:03207
3206
4:03208
3207
4:03209
3208
4:03210
3209
4:03211
3210
Table A-25
Zero adjust progress, MAG 6000
MODBUS regis‐
MODBUS ad‐
ter
dress
4:03212
3211
Modbus RTU RS 485
Operating Instructions, 03/2021, A5E00753974-AB
No. of bytes Data type
2
Word
2
Word
2
Word
2
Word
2
Word
2
Word
2
Word
2
Word
2
Word
2
Word
2
Byte
No. of bytes Data type
2
Byte
Description
System status:
bit0=RunIndicator
bit1=ErrorPendingOn
bit2=ErrPendChanged
bit3=Batching
bit4=BatchPaused
bit5=Zeroadjusting
bit6=Totalizer1Hold
bit7=Totalizer2Hold
Error pending 1* (oldest/first error)
0xFFFF = no error
Error pending 2*
Error pending 3*
Error pending 4*
Error pending 5*
Error pending 6*
Error pending 7*
Error pending 8*
Error pending 9*
Batch status
0 = Idle
1 = Ready
2 = Running
3 = Paused
Description
Zero adjust progress
0 = Idle
1 = Ready
2 = Running
Modbus holding registers
A.12 Flowmeter status
Read / write
R
R
R
R
R
R
R
R
R
R
R
Read / write
R
57