3.1 Technical data

Process medium and scope of application
Flow rate and differential pressure control
with pressure control in district heating sup-
ply networks and industrial plants · Valves
DN 15, 25 and 40 · Pressure rating PN 16
and 25 · Suitable for liquids up to 150 °C
The valve closes when the flow rate, differen-
tial pressure or pressure rises.
Regulator for installation in the low-pressure
pipe, e.g. plant return flow pipe of a district
heating substation.
Min. differential pressure Δp
The minimum required differential pressure
Δp
across the valve is calculated as fol-
min
lows:
Δp
= Δp
min
restriction
Δp
Minimum differential pressure across the valve in bar
min
Δp
Differential pressure created at the restriction for measuring the flow rate
restriction
·
Adjusted flow rate in m³/h
V
K
Valve flow coefficient in m³/h
VS
EB 3131-1 EN
min
·
(
2
)
V
+
K
VS
Design and principle of operation
Dimensions and weights
The lengths and heights in the dimensional
drawings are shown on pages 15 and
16.
Dimensions in mm · Weights in kg
Note
The dimensions and weights of valves with
flanged bodies (DN 40) are the same as
valves with screwed-on flanges.
13