Mitsubishi Electric SUZ-SWM40VA Technical & Service Manual page 32

Hide thumbs Also See for SUZ-SWM40VA:
Table of Contents

Advertisement

OPERATING PROCEDURE
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931, CN932 (Fan motor)
(3) Remove the propeller fan nut.
(4) Remove the propeller fan.
(5) Remove the screws fixing the fan motor.
(6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the screws fixing the relay panel.
(4) Remove the relay panel.
(5) Remove the inverter assembly. (Refer to 2.)
(6) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure
gauge shows 0 kg/cm
(7) Detach the brazed part of the suction and the discharge
pipe connected with compressor.
(8) Remove the compressor nuts.
(9) Remove the compressor.
(10) Detach the brazed parts of 4-way valve and pipe. (Photo 5)
Copyright 2019 MITSUBISHI ELECTRIC CORPORATION
Issued: Dec. 2020 No. OCH718 REVISED EDITION-A
Published: Aug. 2019 No. OCH718
Made in Japan
(0 MPa).
2
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
PHOTOS/FIGURES
Photo 7
Screws of the outdoor fan motor
Photo 8
Brazed part of
the suction pipe
Specifications are subject to change without notice.
32
Propeller fan
nut
Propeller fan
Brazed part of
the discharge pipe
Discharge temperature
thermistor

Hide quick links: