• Auto Operation for Soft Dry
The Setting temperature will be same as that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperature -0.5°C
• Auto Operation for Heating.
Intake Air temp.
Setting temp.
- Compressor ON temperature; Setting temperature
- Compressor OFF temperature; Setting temperature +3°C
Setting temp.
21.5°C
20.5°C
20°C
• 1/f rhythm louver operation : In Auto operation mode, when pressing the vertical air direction control button, lou-
ver moves as following cycle.
MODE0
MODE1
MODE2
MODE3
MODE4
End
MODE5
MODE6
below 20°C
20°C
21°C
20°C
Start
–13–
over 20℃~below 21°C
Intake air temp. +0.5°C
Intake-Air temp.
MODE9
(CLOSED)