Mitsubishi Electric Mr.SLIM PLA-SM71EA Service Manual page 42

Split-type, heat pump air conditioners, split-type, air conditioners, ceiling cassettes r32/r410a, indoor unit, grille
Hide thumbs Also See for Mr.SLIM PLA-SM71EA:
Table of Contents

Advertisement

OPERATING PROCEDURE
4. Removing the room temperature thermistor (TH1)
(1) Remove the electrical box cover. (See Photo 1 and 2)
(2) Disconnect the connector CN20 (Red) from the indoor
controller board.
(3) Remove the room temperature thermistor with its
holder. (See Photo 3)
5. Removing the indoor controller board (I.B)
(1) Remove the electrical box cover. (See Photo 1 and 2)
(2) Disconnect the connectors:
CNMF (White) for fan motor
CNV
(White) for vane motor
CN90 (White) for signal receiver (Option)
CNP
(White) for drain pump
CN4F (White) for float switch
CN44 (White) for thermistor (TH2/TH5)
CN01 (Black) for Indoor/Outdoor connecting line
CN3C (Blue) for Indoor/Outdoor transmission
Disconnect the connectors for optional parts, if any.
(3) For the unit controlled with the wireless remote control-
ler, disconnect the lead wire connected to TB5 on the
indoor controller board.
TB5: Remote controller transmission connecting wire
(4) Remove the indoor controller board (3 holders/4 Hooks).
(See Photo 4)
OCH683
PHOTOS
Photo 3
Electrical box
Indoor controller
board
Electrical box
fixing screw
(M5×10)
Thermistor (TH1)
Photo 4
Holders
42
Thermistor (TH1)
CN20
Electrical box
fixing screw
(M5×10)
Thermistor holder
Hooks

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents